Operation Manual 37107F
MFR 3 - Multi Function Relay
Page 142/165
© Woodward
Para-
meter
Output
Value
Range of the two limit values
11
Analog input [T1]
[°C] or
[°F] or
freely scaleable
0% lower
value
e. g. 0000 corresponds to 000 °C
at temperature input
100% upper
value
e. g. 0255 corresponds to 255 °C
at temperature input
0%
lower value e. g. 0000
corresponds to 00.0 bar oil pressure
100%
upper value e. g. 0100
corresponds to 10.0 bar oil pressure
12
Analog input [T2]
[°C] or
[°F] or
freely scaleable
13
Analog input [T3]
[°C] or
[°F] or
freely scaleable
14
Analog input [T4]
[°C] or
[°F] or
freely scaleable
15
Analog input [T5]
[°C] or
[°F] or
freely scaleable
16
Analog input [T6]
[°C] or
[°F] or
freely scaleable
17
Analog input [T7]
[°C] or
[°F] or
freely scaleable
18
additional freely scaleable analog in-
put (terminal 91, 92)
19
Mains real power
[kW]
0%
lower value
e. g. -0800 kW
100% upper
value
e. g. 0800 kW
20
Mains apparent power in L1
[A]
0%
lower current value
e. g. 0000 A
100%
upper current value
e. g. 500 A
21
Mains power factor
[e. g. (-070 to +080) /100]
(find definition at the end
of this table)
[dimensionless]
0%
lower difference to power factor = 1
e. g. -0030 corresponds to c0.70
100%
upper difference to power factor = 1
e. g. 0030 corresponds to i0.70
22
Mains re-active power
[kvar]
0%
capacitive re-active power (negative)
e. g. -0100 kvar
100%
inductive re-active power (positive)
e. g. +0100 kvar