Installation
2
017-
03
25
The mounting location should be well accessible for mounting and electrical installation. Make
sure that there is enough space to open the enclosure cover and to access the terminals,
switches, and cable glands. Choose a mounting location that meets the requirements of the
climatic limits specified in the technical data.
The enclosure has a degree of protection of IP65 and is designed for wall mounting (mounting
accessories and tools not included). See table "Installation torque for cable glands and
Required tools:
■
2 screws (M6)
■
Drill
■
Screwdriver
Depending on the mounting surface, you may need additional mounting material.
Danger!
Danger to life from electric shock through degree of protection violation
Failing to ensure the degree of protection for the enclosure according to EN 60529 can result in
severe or lethal electric shock.
Ensure that the enclosure meets the required degree of protection during mounting and
installation activities:
- All seals must be undamaged and correctly fitted
- All screws of the housing/housing cover must be tightened with the appropriate torque
- Only cables of the appropriate size must be used in the cable glands
- All cable glands must be tightened with the appropriate torque
- All unused cable glands must be sealed or plugged with corresponding stopping plugs
Danger!
Explosion hazard from overvoltage
Using accessories or devices that are not suitable for the specified overvoltage category can
lead to added voltages. This can result in a voltage flashover generating sparks. The sparks
can ignite the surrounding potentially explosive atmosphere.
Ensure that all circuits connected to the device comply with the overvoltage category II (or
better) according to IEC/EN 60664-1.
Danger!
Danger to life from using damaged or repaired devices.
Using a defective or repaired device can compromise its function and its electrical safety.
■
Do not use a damaged or polluted device.
■
The device must not be repaired, changed or manipulated.
■
If there is a defect, always replace the device with an original device from Fuchs.