2
017-
03
28
Installation
Straight-Through or Crossover Wiring
Depending on the network topology, use straight-through or crossover wiring to connect the
WirelessHART gateway to an Ethernet access point. Note that newer Ethernet hubs, switches,
and routers are able to detect whether straight-through wiring or crossover wiring has been
used and adjust the pinout automatically if necessary.
Wiring with a T568A Plug
Witing with a T568B Plug
3.6
Preparing RS-485 Connection
The WirelessHART gateway is equipped with a fully galvanic isolated RS-485 interface. Note
that the maximum length of the cable running from the WirelessHART gateway to the process
control system is 1200 m or less, depending on the cable type and transfer rate. Use shielded
twisted pair (STP) cables only. Ensure sufficient relief of tension on the cables during
installation and note the minimum bending radii of the cables.
Terminal block an
WirelessHART gateway
Straight-through
Crossover
T1
Brown
Brown
White/brown stripe
White/brown stripe
T2
Blue
Blue
White/blue stripe
White/blue stripe
RX-
Orange
Green
RX+
White/orange stripe
White/green stripe
TX-
Green
Orange
TX+
White/green stripe
White/orange stripe
SHD
Cable shield
Cable shield
Terminal block an
WirelessHART gateway
Straight-through
Crossover
T1
Brown
Brown
White/brown stripe
White/brown stripe
T2
Blue
Blue
White/blue stripe
White/blue stripe
RX-
Green
Orange
RX+
White/green stripe
White/orange stripe
TX-
Orange
Green
TX+
White/orange stripe
White/green stripe
SHD
Cable shield
Cable shield