background image

12

Wilo-WiBooster - Installation and Operation Manual

7.2.2

Programmable Logic Controller Features
The Wilo-WiBooster boosting system technology is the 

current state of the art functionality and factory-checked 

to ensure it performs at start-up.

 The programmable logic 

controller shall have the following attributes:

•  7” LED color touchscreen with a display resolution of 

800 x 480 pixels. 

•  The PLC shall indicate on the display, per the pump 

Icon, the individual pump status in real-time.  

(green=running, red=faulted, no color=off). 

•  The PLC shall be factory set for either base load/peak 

load or duty/standby operation.

•  The PLC shall provide off/hand/auto function. Hand 

operation shall be password protected.

•  The PLC shall display pump hours, suction PSI, discharge 

PSI, pump frequencies, total kWh for system, and 

current kWh per pump.

•  The PLC shall be able to modify the discharge pressure 

setting through password protected screen.

•  The PLC shall have a low pressure cut out function.

•  The PLC shall have pipe burst protection.

• 

The PLC shall be able to be able to flash the PLC 

program by means of a Micro-SD card via Micro-SD port 

or remotely flashed by the factory (note: internet access 

need in order to be flashed remotely).

•  The PLC shall have a RJ45 Ethernet port capable of 

transmitting data 10/100Mbps using a Cat 5 cable.

•  The PLC shall have a 2.0 USB port available for 

communication.

•  The PLC shall have onboard Modbus Protocol. Two serial 

ports available; one for communication to the VFD and 

one open for the building management system.

•  The PLC shall have the following I/O:

•  Number of digital inputs: 18

•  Number of digital outputs: 17

•  Number of analog inputs: 4

•  Number of analog outputs: 4

Optional panel items include

•  NEMA 3R panel suitable for outdoor applications.

•  Run/fault lights per pump

•  Surge protection

•  Interior panel light

•  Transformer

•  NEMA 3R transformer cover

•  BACnet gateway

•  LONworks gateway

•  CANopen gateway card

7.2.3

Sequence of Operations

1. 

When pressure drops low of the pressure band, first pump 

will turn on.

2.  The pump will adjust speed to maintain pressure at the 

set point.

3.  Additional pumps will turn on to maintain pressure if 

demand cannot be met with one pump.  In systems with 

more than 2 pumps, there will be a delay between each 

additional pump turning on.

4.  When additional pumps turn on, they will adjust in speed 

so that all pumps run at the same speed. 

5.  When multiple pumps are running, one will turn off if 

either:

a.  Pressure is high out of band for a programmable 

amount of time.

b.  System will periodically check whether fewer pumps 

can maintain pressure efficiently and if so, a pump 

will turn off.

6.  If only 1 pump is running, the pump will turn off if either:

a.  Pressure is high out of band for a programmable 

amount of time.

b.  .System will periodically boost pressure a 

programmable amount above the set point.  If 

pressure does not drop after returning the set point 

to normal, the pump will turn off.

  01 Home Screen

1.  Battery indicator

a.  Not visible until battery level is low.  Battery is sup-

posed to last for around 7 years.  If battery fails, PLC 

time/date information as well as any saved data will 

be lost if power is lost.  Battery can be replaced while 

power is running to maintain data, although battery 

warning will not clear until power is cycled.

2.  Hand Control indicator

a.  Displays a warning that PLC is currently in hand control 

mode.  PLC will not respond automatically to pressure 

changes when in this mode.  Pumps can be turned 

off from the main screen during hand control, unless 

the hand control alarm override is active.  In that case, 

pumps can only be controlled from the hand control 

screen.

3.  Active Alarms

a.  Will cycle through all currently active alarms every few 

seconds.

b.  Only visible if at least one alarm is active.

c.  Can be clicked to view active alarms.

4.  Pump information (Icon for pump will change based on 

booster model)

a.  The pump icons display whether pumps are on, off, or 

faulted

i.  Cyan indicates the pump is running

ii.  Grey indicates that the pump is off

iii. Orange indicates the pump has faulted

b.  The switch below the pump icons will take the pumps 

from auto to off. 

c.  The bar below the auto/off switch show pump speed.  

A fully green bar is full speed while an empty bar is off.  

Indication is based on full 0-60Hz, so a pump running 

at a minimum speed of 30Hz will show the bar half 

green.  If max frequency is changed to 50Hz, bar will be 

scaled from 0-50Hz. 

5.  Suction and discharge pressure

a.  Show current suction and discharge pressures

b.  Suction pressure will not display if suction pressure 

transducer is not used

6.  Standby pump indicator

a.  A standby pump can be set in the options menu.  If 

using one standby pump, the pump with the highest 

runtime will be the standby pump until all pumps are 

off, then a new pump is evaluated for standby if the 

highest runtime pump has changed. With 2 standby 

pumps, the highest 2 runtime pumps are set to standby.

b.  Standby pump will not run unless a pump has faulted or 

is taken to off.

7.  System information button

a.  Goes to system information screen.  No password 

required

8.  Operator settings button

a.  Goes to operator settings screen.  Password 1111

9.  Advanced settings button

a.  Goes to advanced settings screen.  Password 2222

10.  Silence Button

a.  Not used. Touch screen to silence alarms.

2

4

1

3

5

7

8

9

6

10

Summary of Contents for WiBooster

Page 1: ...Installation and operating instructions WILO_IOM_WIBOOSTER_07012019 Wilo WiBooster Pressure Boosting Systems...

Page 2: ...ages In detail non observance can for example result in the following risks Failure of important pump unit functions Failure of required maintenance and repair procedures Danger to persons from electr...

Page 3: ...re function and requirements comply with the following guidelines and directives NSF 61 and NSF 372 listed for drinking water certification DOE regulations The Wilo WiBooster pressure boosting system...

Page 4: ...th vibration damper 2 2 to 4 Close Coupled Series 230 or 320 centrifugal pumps 3 Control panel that contains one variable frequency drive per pump 4 Suction manifold 5 Check valve 6 Isolation butterfl...

Page 5: ...5 Wilo WiBooster Installation and Operation Manual Figure 5c Figure 5d...

Page 6: ...l Figure 5e WARNING Risk of damage or bodily injury Please follow the above instructions figure 5d in order to safely remove the hydropneumatic tank from the discharge manifold for service Note The bl...

Page 7: ...rovided from the water main Its analog signal is processed by the PLC to make sure it does not fall below the suction pressure set point In the case of an indirect connection system separation through...

Page 8: ...secure the pipe clamps to the Wilo WiBooster manifolds The connection is made either on the right or left of the system depending on the site conditions It may be necessary to move blind flanges or t...

Page 9: ...ccordance to local and national electrical codes The connections intended for this purpose are identified accordingly see wiring diagram Further measures are referenced in the wiring diagram of the co...

Page 10: ...Local Codes Fuses LP J for 1 1 4 X Full Load Amps of Both Motors SHORT CIRCUIT CURRENTD Branch Circuit Protection 8199 FIELD CONNECTIONS Installer To Supply Branch Circuit NUMBER ON TERMINAL BLOCKS C...

Page 11: ...L1 L3 L2 L3 L2 L1 1L1 1L3 1L2 W V U MP3 VFD3 31 MOTOR PUMP 33 32 3 86 87 88 L3 L2 L1 2L2 2L1 AN0 AN1 AN2 AN3 ACM 0 VDC SUCTION TRANSDUCER DISCHARGE TRANSDUCER V 24 VDC 0V 0 VDC GROUND START RUN ENABLE...

Page 12: ...umps can maintain pressure efficiently and if so a pump will turn off 6 If only 1 pump is running the pump will turn off if either a Pressure is high out of band for a programmable amount of time b Sy...

Page 13: ...sets the desired output pressure of the system 04 Pump Test Run The Pump Test Run page allows for pumps to be run for a short duration 1 Enables and disables the pump test option When enabled pumps wi...

Page 14: ...s with alarm conditions in Activating this mode will allow the user to run the pumps unless regardless of conditions unless the pump failure is due to a physical failure of the pump or drive This opti...

Page 15: ...free email accounts like gmail or outlook will not work Accounts with https www smtp2go com have been verified to work 2 Port number associated with mail server Default 587 3 Email user name This is t...

Page 16: ...Sensor faults activate immediately upon an invalid value A failed low sensor fault will show a negative value of pressure A failed high sensor fault will show the max value of pressure A failed high...

Page 17: ...the internal IP address which can be found on the PLC by clicking Menu Page IP Configuration from the main page 2 If connecting to the PLC from outside the network enter the WAN address of your networ...

Page 18: ...b Max frequency Default value 60 Hz Input range 25 60 Hz 17 Pipe Fill Settings Pipe Fill Mode will only allow one pump to run until either the pressure or time requirement is met 1 Enables and disabl...

Page 19: ...ed or shut off Check inlet pipe if necessary remove blockage or open check valve Nominal diameter of inlet pipe too small Check the inlet pipe increase the crosssection for the inlet pipe if necessary...

Page 20: ...sary Inlet pipe incorrectly installed Check inlet pipe if necessary change pipe routing Air in inlet Check if necessary seal pipe Vent pumps Impellers blocked Check pump if necessary replace or have r...

Page 21: ...k pressure to the correct level Isolate see step 1 of figure 5d the pumps and system from the discharge side and upstream piping of the manifold Drain the water from the discharge manifold Check the g...

Page 22: ...WILO USA LLC 1 262 204 6600 www wilo usa com info us wilo com WILO Canada Inc 1 403 276 9456 www wilo canada com info wilo canada com WILO Mexico 52 442 167 00 32 www wilo mexico com info wilo com mx...

Reviews: