background image

9

WILO_IOM_WIBOOSTER_07012019

6.2.4

Dry-running protection system and protection against 

low water

•  Every Wilo-WiBooster pressure booster system is 

supplied with a suction transducer that has a .4% 

accuracy across its full span (0-150 PSI) which equates 

to a +/- 0.6 PSI deviation.

• 

To fit an alternate, dry-running, switch protection 

system (

not common

 and provided by others):

•  It is very rare for a problem to arise using the Wilo-

WiBooster supplied suction transducer when a 

storage tank is used. Regardless of this rarity, issues 

with low water conditions when utilizing a storage 

tank can occur and a digital switch can be used in 

lieu of the transducer in the form of a tank float or 

low water probe. 

•  Please refer to the PLC operation, described later 

in this document for detailed instructions to use a 

digital switch in lieu of the Wilo-supplied suction 

transducer.

6.2.5

Diaphragm pressure vessel (optional accessory)

For transport reasons, if the NSF-61 hydropeumatic has 

been purchased as an accessory for the Wilo-WiBooster, 

it will not be attached upon delivery; it will be separately 

packed. Before commissioning, this must be mounted 

on the ¾” shutoff valve (see Fig. 5e) and charged to the 

appropriate pressure at the jobsite with nitrogen (See below 

– 6.2.5.1)

6.2.5.1

Diaphragm pressure vessel recommended charge

The hyropneumatic tank should be installed on the 

discharge manifold, adjacent to the pressure transducer, 

and it should be charged with pressure to equal 70% of 

the system constant pressure setpoint.  For example, if the 

constant pressure setpoint is 80 PSI, the tank should be 

charged to 56 PSI (80 x 70%).

6.3                

Electrical connection

                             

DANGER!

Risk of fatal injury! The electrical connection must be 

made in accordance with the local and national electrical 

code regulations by a qualified electrician!

The Wilo-WiBooster can be equipped with different 

variances of current and voltage. To make the electrical 

connection, the corresponding installation and operating 

instructions and attached electrical circuit diagrams must be 

observed. General points to be considered are listed below:

•  Every Wilo-WiBooster control panel is supplied with a 

current overload sized for each pump motor amperage 

(circuit breakers).

•  The type of current and voltage of the main connection 

must comply with the details on the wiring diagram of 

the control panel.

•  The electrical connection line must be adequately sized 

according to the total power of the Wilo-WiBooster.

•  External protection must be provided according to local 

and national electrical codes.

•  As a protective measure, the Wilo-WiBooster must be 

wired to ground in accordance to local and national 

electrical codes. The connections intended for this 

purpose are identified accordingly (see wiring diagram).

•  Further measures are referenced in the wiring diagram 

of the control panel.

7                              

Commissioning/decommissioning

We recommend that Wilo’s after-sales service commission 

the system. Contact your dealer, the nearest Wilo 

representative or our service department directly for details.

7.1                

General preparations and checking

                             

WARNING!

Make sure the system is de-engergized and wait 5 

minutes to allow any capacitance voltage to discharge.

 

Before energizing the system for the first time:

•  Check that onsite wiring and grounding of the electrical 

panel is correct.

•  Check that the pipe joints are stress-free.

•  Fill the system and check visually for leakage.

• 

Open the pump vent screws and slowly fill the pumps 

with water so that the air can escape.

                             

CAUTION!

Risk of damage! Do not allow the pump to run dry. Dry-

running destroys the axial face seal of the Scot Pump.

In suction mode (e.g. negative level difference between 

storage tank and pumps), the pump and the suction line 

must be filled via the opening in the vent screw (use a 

funnel as required).

7.2                

Electrical layout, sequence of operations and start-up 

procedure

                             

DANGER!

Risk of fatal injury! Always refer to the wiring diagram 

of the onsite Wilo-WiBooster ONLY! References and 

examples of wiring diagrams in this document are not 

official wiring diagrams for the onsite unit in the panel.

7.2.1

Electrical layout - panel overview

Every Wilo-WiBooster panel shall meet the requirements 

of UL508A standards for Industrial Control equipment. 

Standard panel shall be rated as a NEMA 12 enclosure with 

a fan; CFM rated for heat sink requirements of the variable 

frequency drives (VFDs). Three phase, 208-230/460 

voltage panels shall either be equipped and mounted with 

Danfoss FC-51 micro VFDs (1-10 horse power) or Danfoss 

FC-101 VFDs (10-20 horse power) – no keypad per pump. 

Three Phase, 575 voltage panels shall be equipped and 

mounted with Danfoss FC-101 drives – no keypad per 

pump. VFD’s shall be programed to the WIlo-WiBooster 

needed parameters prior to shipment. The Danfoss variable 

speed drives will be mounted inside the panel enclosure 

and supplied with a NEMA 1 enclosure rating. The VFD will 

utilize the MODbus protocol to report faults and energy 

usage in kWh to the programmable logic controller. The 

VFD shall provide visual indication that requires no external 

control devices. The panel shall have labeled wires and 

terminal block for easy reference to the wiring diagram. 

The panel shall contain motor protector circuits, for each 

pump supplied, sized for motor amperage. Through-the-

door-disconnect with selector handle and lockout will be 

provided with the panel. The panel will also be provided with 

alarm with silencing button.

Summary of Contents for WiBooster

Page 1: ...Installation and operating instructions WILO_IOM_WIBOOSTER_07012019 Wilo WiBooster Pressure Boosting Systems...

Page 2: ...ages In detail non observance can for example result in the following risks Failure of important pump unit functions Failure of required maintenance and repair procedures Danger to persons from electr...

Page 3: ...re function and requirements comply with the following guidelines and directives NSF 61 and NSF 372 listed for drinking water certification DOE regulations The Wilo WiBooster pressure boosting system...

Page 4: ...th vibration damper 2 2 to 4 Close Coupled Series 230 or 320 centrifugal pumps 3 Control panel that contains one variable frequency drive per pump 4 Suction manifold 5 Check valve 6 Isolation butterfl...

Page 5: ...5 Wilo WiBooster Installation and Operation Manual Figure 5c Figure 5d...

Page 6: ...l Figure 5e WARNING Risk of damage or bodily injury Please follow the above instructions figure 5d in order to safely remove the hydropneumatic tank from the discharge manifold for service Note The bl...

Page 7: ...rovided from the water main Its analog signal is processed by the PLC to make sure it does not fall below the suction pressure set point In the case of an indirect connection system separation through...

Page 8: ...secure the pipe clamps to the Wilo WiBooster manifolds The connection is made either on the right or left of the system depending on the site conditions It may be necessary to move blind flanges or t...

Page 9: ...ccordance to local and national electrical codes The connections intended for this purpose are identified accordingly see wiring diagram Further measures are referenced in the wiring diagram of the co...

Page 10: ...Local Codes Fuses LP J for 1 1 4 X Full Load Amps of Both Motors SHORT CIRCUIT CURRENTD Branch Circuit Protection 8199 FIELD CONNECTIONS Installer To Supply Branch Circuit NUMBER ON TERMINAL BLOCKS C...

Page 11: ...L1 L3 L2 L3 L2 L1 1L1 1L3 1L2 W V U MP3 VFD3 31 MOTOR PUMP 33 32 3 86 87 88 L3 L2 L1 2L2 2L1 AN0 AN1 AN2 AN3 ACM 0 VDC SUCTION TRANSDUCER DISCHARGE TRANSDUCER V 24 VDC 0V 0 VDC GROUND START RUN ENABLE...

Page 12: ...umps can maintain pressure efficiently and if so a pump will turn off 6 If only 1 pump is running the pump will turn off if either a Pressure is high out of band for a programmable amount of time b Sy...

Page 13: ...sets the desired output pressure of the system 04 Pump Test Run The Pump Test Run page allows for pumps to be run for a short duration 1 Enables and disables the pump test option When enabled pumps wi...

Page 14: ...s with alarm conditions in Activating this mode will allow the user to run the pumps unless regardless of conditions unless the pump failure is due to a physical failure of the pump or drive This opti...

Page 15: ...free email accounts like gmail or outlook will not work Accounts with https www smtp2go com have been verified to work 2 Port number associated with mail server Default 587 3 Email user name This is t...

Page 16: ...Sensor faults activate immediately upon an invalid value A failed low sensor fault will show a negative value of pressure A failed high sensor fault will show the max value of pressure A failed high...

Page 17: ...the internal IP address which can be found on the PLC by clicking Menu Page IP Configuration from the main page 2 If connecting to the PLC from outside the network enter the WAN address of your networ...

Page 18: ...b Max frequency Default value 60 Hz Input range 25 60 Hz 17 Pipe Fill Settings Pipe Fill Mode will only allow one pump to run until either the pressure or time requirement is met 1 Enables and disabl...

Page 19: ...ed or shut off Check inlet pipe if necessary remove blockage or open check valve Nominal diameter of inlet pipe too small Check the inlet pipe increase the crosssection for the inlet pipe if necessary...

Page 20: ...sary Inlet pipe incorrectly installed Check inlet pipe if necessary change pipe routing Air in inlet Check if necessary seal pipe Vent pumps Impellers blocked Check pump if necessary replace or have r...

Page 21: ...k pressure to the correct level Isolate see step 1 of figure 5d the pumps and system from the discharge side and upstream piping of the manifold Drain the water from the discharge manifold Check the g...

Page 22: ...WILO USA LLC 1 262 204 6600 www wilo usa com info us wilo com WILO Canada Inc 1 403 276 9456 www wilo canada com info wilo canada com WILO Mexico 52 442 167 00 32 www wilo mexico com info wilo com mx...

Reviews: