background image

English

4

WILO SE 03/2009

3 Transport and interim storage

When receiving the material, check that there has 
been no damage during the transport. If shipping 
damage has occurred, take all necessary steps with 
the carrier within the allowed time.

Handle the pump carefully so as not to damage the 
unit prior to installation.

4 Intended use (Application)

This pump's basic function is to pump warm or cold 
water or other low viscosity fluids that contain no 
mineral oil, abrasive substances or materials having 
long fibres. The manufacturer's approval is required 
for use to pump corrosive chemicals. 

Application areas:

• water distribution and boosting installations
• industrial  circulation systems
• process  fluids
• cooling water circuits
• fire-fighting and washing stations
• watering installations, etc.

5 Technical data

5.1 Type key

Outline and pipe dimensions (see: Fig. 2)

5.3 Scope of Supply 

• Complete pump  and motor, NPT companion flanges, 

bolts and flange gaskets

• Installation and operating instructions

CAUTION! Outside influences may cause damages
If the delivered material is to be installed later on, 
store it in a dry place and protect it from impacts 
and any outside influences (humidity, frost etc.).

CAUTION! Possible damage of the pump
These pumps are intended for use with water only 

Example: MVIS15-02-1/O/K/3-460-60-2

MVIS

Pump family

15

Nominal flow rate in GPM at 60Hz / 2 poles

- 02

Number of stages

- 1

1 = Stainless steel 304

/ O

O = Oval flange 250 # with NPT companion flange

/ E

E = 

E

PDM o'ring

/ 3

3 = Three phase

- 460

230 = 208-230 V
460 = 460 V
575 = 575 V

- 60

60 = 60 HZ

- 2

2 = 2 poles

5.2

Data table

Maximum operating pressure

Pump casing:

230 PSI (16 bar)

Maximum suction pressure:

140 PSI (10 bar)

Temperature range
Liquid temperatures

14°F to 122°F 
(- 10° to + 50 °C)

Ambient temperature

+104°F Max (+ 40 °C)

Electrical data

Motor Protection class:

NEMA 2

Insulation class:

H

Frequency

60 Hz

Voltages

3

~

: 208-230 V, 460 V, 575 V  

(± 10 %)

Others

Minimum suction head:

3 ft  (1 m)

Ambient humidity:

<90 %

Types 

Dimensions (inch) 

MVIS15-02 to  MVIS15-08

3

15

/

16

7

1

/

16

8

2

15-22

3

/

4

 

6

3

/

8

NPT 1" 

3

  Ø ½

M10  

MVIS30-02 to  MVIS30-06

3

15

/

16

7

1

/

16

8

2

16-20

3

/

4

6

3

/

8

NPT 1"¼

3

 Ø ½

M10  

MVIS50-02 to  MVIS50-03

5

1

/

8

10

10

1

/

8

3

1

/

16

17-20

3

/

4

7

7

/

8

NPT 1"½

4

 Ø ½

M12  

Types 

Dimensions (mm) 

MVIS15-02 to  MVIS15-08

100

180

157

212

204

50

378-548

20

160

NPT 1" 

75

Ø12 

M10 

MVIS30-02 to  MVIS30-06

100

180

157

212

204

50

398-500

20

160

NPT 1"¼

75

Ø12 

M10 

MVIS50-02 to  MVIS50-03

130

215

187

252

250

80

425-485

20

200

NPT 1"½

100

Ø 12 

M12 

Summary of Contents for MVIS 15

Page 1: ...2 065 408 03 2009 GRD Wilo MVIS 15 30 50 GB Installation and operating instructions F Notice de montage et de mise en service E Instrucciones de instalaci n y funcionamiento...

Page 2: ...Fig 1 Fig 2 R D S K U H C M A T B L P F E Fig 3 Fig 4 S1 L1 L2 L3 S2 K K K 3 P1 P2 L1 L2 L3...

Page 3: ...GB Installation and operating instructions 3 F Notice de montage et de mise en service 9 E Instrucciones de instalaci n y funcionamiento 15...

Page 4: ...aims In particular failure to comply with these safety pre cautions could increase the possibility of the follow ing risks the failure of important parts of the pump or instal lation personal injury d...

Page 5: ...d any outside influences humidity frost etc CAUTION Possible damage of the pump These pumps are intended for use with water only Example MVIS15 02 1 O K 3 460 60 2 MVIS Pump family 15 Nominal flow rat...

Page 6: ...hook or a ring of sufficient capacity total weight of pump to allow the use of a hoist or similar device for the servicing and repair of the pump When fitting the oval flange only the screws sup plied...

Page 7: ...ed liquid flows The escaping air produces a clearly audible whistle Retighten the air bleed screw Slowly open the isolation valve on the discharge side The gauge on the discharge side is used to monit...

Page 8: ...if there is no risk of frost If the place of installation is not protected from frost the pumps and pipes must be emptied for the winter Close the isolation valves open the discharge screws at the bas...

Page 9: ...S BUT PROVIDES IN SUFFICIENT FLOW AND OR PRES SURE a Wrong direction of rotation a Check the direction of rotation of the motor and correct it if necessary b Pipe obstructed by foreign material b Chec...

Page 10: ...accro tre la probabilit des risques suivants d faillance de fonctions importantes de la pompe ou de l installation dangers pour les personnes par influences lectrique ou m canique dommages mat riels 2...

Page 11: ...s impacts et de toutes influences ext rieures humidit gel etc ATTENTION Risque d endommager la pompe Ces pompes conviennent uniquement au refoulement de l eau Exemple MVIS15 02 1 O K 3 460 60 2 MVIS F...

Page 12: ...et plane Toute inclinaison de la pompe provoque l usure pr matur e du palier Installer la pompe sur un massif mini 10 cm 4 de haut Pr voir un mat riaux isolant li ge ou caout choux arm sous la pompe...

Page 13: ...tiquette de la pompe Le c ble de raccordement doit tre plac de fa on ne jamais entrer en contact avec la canalisation prin cipale et ou le corps de pompe et la carcasse moteur La pompe installation do...

Page 14: ...r FIG 3 rep 6 et la vis AVERTISSEMENT Blessure corporelle Pompe sous pression Lorsque l on travaille avec des temp ratures de liquides refoul s lev es et des pressions importantes le jet s chappant de...

Page 15: ...10 2 La pompe fonctionne mais ne refoule pas sufisamment a Sens de rotation incorrect a V rifier le sens de rotation du moteur et l inverser au besoin b La conduite est obstru e par des corps tranger...

Page 16: ...de mante nimiento y reparaci n Lesiones personales debidas a causas el ctricas mec nicas o bacteriol gicas Da os materiales 2 4 Instrucciones de seguridad para el operador Deber n cumplirse las norma...

Page 17: ...factores externos humedad heladas etc Atenci n Riesgo de da ar la bomba Estas bombas s lo son tiles para la conexi n de salida del agua Ejemplo MVIS15 02 1 O K 3 460 60 2 MVIS Familia de bomba 15 Caud...

Page 18: ...ca el desgaste con mayor rapidez del cojinete Instale la bomba sobre un masivo m nimo 10 cm 4 de altura Prevea un material aislante corcho o cau cho armado bajo la bomba para evitar las molestias sono...

Page 19: ...entre en contacto con la canalizaci n principal y o con el cuerpo de la bomba y la carcasa del motor La bomba instalaci n debe estar conectada a tierra siguiendo las regulaciones locales Un interrupto...

Page 20: ...abajamos con temperaturas de l quidos de impulsi n muy altas y con presiones importantes los chorros que se escapan del tornillo de la purga de aire pueden ocasionar quemaduras y heridas Por este moti...

Page 21: ...ombas y los con ductos durante el invierno Cierre las v lvulas de corte abra las v lvulas de drenaje en el pie de la bomba Ver FIG 3 rep 6 y el tornillo de purga de aire Ver FIG 3 rep 5 Es imprescindi...

Page 22: ...pero no tiene suficiente presi n a Sentido de rotaci n incorrecto a Compruebe el sentido de rotaci n e invi rtalo si es necesario b El conducto se encuentra obstruido por cuerpos extra os b Controle...