Delay
OFF
-Alarm delay switched off.
<§>
1 ... 8000 s
-Alarm is delayed by selected time.
Self-retaining off
No self-holding of the temperature alarm.
<§>
on
An activation of the
-
alarm will be stored. The
-
alarm
can be acknowledged in the window ”Monitoring“.
Start
suppression
OFF
Without start up
Start-up
-
alarm suppression switched off
<§>
Start up
Suppression
active
Start-up
-
alarm suppression active:
Temperature must be within the limits once. Only then
the
-
alarm is activated when reaching the alarm value.
Display col-
our
Red
The monitoring displays the
-
alarm in red colour.
<§>
Green
Intended for enabling signals: Display colour is green.
Orange
Switching
behaviour
Direct
The monitoring output is activated when the max. limit
value has been exceeded or if the min. limit value has
been undercut.
Inverse
The signal is inverted and output to the monitoring.
If the min. limit value has been exceeded or if the max.
limit value has been undercut the output is set.
Wizard
The wizard serves as a support for initial commis-
sioning of the controller or in the occasion of a
reconfiguration.
Please notice the wise order in which the parame-
ters of the wizard have to be adjusted.
The wizard can be cancelled at any time.
By pressing the arrow keys you will move on to
the next step.
Pressing the OK-key will lead to the parameters.
New controllers automatically start with the wizard. After pressing “finish” in the last window
of the wizard the wizard will not be shown anymore at startup.