Manual: R4000-XX-X-000-X-X_EN
Release: 1.20
©Elotech GmbH
Seite 5 / 48
4
Connection Diagram
Option continuous
Ground connection
The Ground connection
(flat plug 6,3mm) must be connected to an earth rail via a thick cable (>=4qmm) in the
shortest possible way (<20cm)!
4.1
Connection Diagram:
Power supply, Logic Inputs and Heater Current
Function of the logic inputs:
In_1: 0 = Setpoint 1 active for all
zones.
1 = Setpoint2 active for all
zones.
In_2: 0 = Parameter “Authorisation”
is adjustable.
1 = Parameter “Authorisation”
is not adjustable.
In_3:
no function
In_4:
no function