Menu: Sensor settings
All parameters for sensor configuration
Sensor
Description see 0
Configuration sensors
Process offset
-999..0..1000°C
<§= 0°C>
This parameter serves to correct the input signal:
- the correction of a gradient between the
measuring point and the sensor tip
- line resistance balancing at 2-wire-RTD
- Correction of the control deviation when
using P or PD action.
If for example the offset value is set to +5°C, then
the real temperature measured by the sensor is
5°C less than the displayed actual process value.
Make sure that the adjusted actual temperature
value should not fall below or exceed the measur-
ing range limits.
Setpoint min.
MR-Start ...
Setpoint max.
Lowest adjustable setpoint value.
<§ = 0>
MR-Start: Start of measurement range
Setpoint max.
Setpoint min …
MR-End
Highest adjustable setpoint value.
<§= 400>
MR-End: End of measurement range
The minimal span of linear value min. and max. is 100, the maximal span is 2000.
Linear value min.
For linear meas-
urement range
only
-900 …
(Linear value max.
-100)
Measuring range starting value of the linear scale.
<§= 0,0>
Linear value max.
For linear meas-
urement range
only
(Linear value min.
+100) … 10.000
Measuring range final value of the linear scale.
<§= 100,0>
Decimal
For linear meas-
urement range
only
0 … 2
Decimal of the linear measuring range.
<§= 1>
Unit zone
°C … °F
For
control
zones, you can choose between ° C
and ° F.
<§=°C>
The temperature values of the selected zone are
set to the specified unit with this parameter. Please
check all temperature values after adjustment.
(Limit values, setpoints, setpoint limits, actual value
offset and, if applicable, the linear limits.)
°C, °F, OFF, %, A,
V, Hz, rpm, U/min,
bar, psi, Pa, l/min,
m³, l, m/s, m²/s,
Numerous units can be set in
display
zones.
<§=OFF>
No unit = OFF