56
10 Supplement
WIKA Operating Instructions - Process pressure transmitter CPT-2x
Nominal range
Overload capability
Maximum pressure
Minimum pressure
0 … +2.5 bar/0 … +250 kPa
+50 bar/+5000 kPa
-1 bar/-100 kPa
0 … +5 bar/0 … +500 kPa
+65 bar/+6500 kPa
-1 bar/-100 kPa
0 … +10 bar/0 … +1000 kPa
+90 bar/+9000 kPa
-1 bar/-100 kPa
0 … +25 bar/0 … +2500 kPa
+125 bar/+12500 kPa
-1 bar/-100 kPa
0 … +60 bar/0 … +6000 kPa
+200 bar/+20000 kPa
-1 bar/-100 kPa
0 … +100 bar/0 … +10000 kPa
(only for measuring cell ø 28 mm)
+200 bar/+20000 kPa
-1 bar/-100 kPa
-1 … 0 bar/-100 … 0 kPa
+35 bar/+3500 kPa
-1 bar/-100 kPa
-1 … +1.5 bar/-100 … +150 kPa
+40 bar/+4000 kPa
-1 bar/-100 kPa
-1 … +10 bar/-100 … +1000 kPa
+90 bar/+9000 kPa
-1 bar/-100 kPa
-1 … +25 bar/-100 … +2500 kPa
+125 bar/+12500 kPa
-1 bar/-100 kPa
-1 … +60 bar/-100 … +6000 kPa
+200 bar/+20000 kPa
-1 bar/-100 kPa
-1 … +100 bar/-100 … +10000 kPa
(only for measuring cell ø 28 mm)
+200 bar/+20000 kPa
-1 bar/-100 kPa
-0.025 … +0.025 bar/-2.5 … +2.5 kPa
+5 bar/+500 kPa
-0.05 bar/-5 kPa
-0.05 … +0.05 bar/-5 … +5 kPa
+15 bar/+1500 kPa
-0.2 bar/-20 kPa
-0.2 … +0.2 bar/-20 … +20 kPa
+20 bar/+2000 kPa
-0.4 bar/-40 kPa
-0.5 … +0.5 bar/-50 … +50 kPa
+35 bar/+3500 kPa
-1 bar/-100 kPa
Absolute pressure
0 … 0.1 bar/0 … 10 kPa
15 bar/1500 kPa
0 bar abs.
0 … 1 bar/0 … 100 kPa
35 bar/3500 kPa
0 bar abs.
0 … 2.5 bar/0 … 250 kPa
50 bar/5000 kPa
0 bar abs.
0 … +5 bar/0 … +500 kPa
65 bar/+6500 kPa
0 bar abs.
0 … 10 bar/0 … 1000 kPa
90 bar/9000 kPa
0 bar abs.
0 … 25 bar/0 … 2500 kPa
125 bar/12500 kPa
0 bar abs.
0 … 60 bar/0 … 6000 kPa
200 bar/20000 kPa
0 bar abs.
0 … 100 bar/0 … +10000 kPa
(only for measuring cell ø 28 mm)
200 bar/20000 kPa
0 bar abs.
Nominal measuring ranges and overload capacity in psi
Nominal range
Overload capability
Maximum pressure
Minimum pressure
Gauge pressure
0 … +0.4 psig (only for measuring cell ø 28 mm)
+75 psig
-0.7 psig
0 … +1.5 psig
+225 psig
-3 psig
0 … +5 psig
+375 psig
-11.50 psig