41
6 Set up with the display and adjustment module
WIKA Operating Instructions - Process pressure transmitter CPT-2x
Select the requested simulation variable and set the requested value.
To deactivate the simulation, you have to push the
[ESC]
key and
confirm the message "
Deactivate simulation
" with the
[OK]
key.
Caution:
During simulation, the simulated value is output as digital signal.
The status message along with the Asset Management function is
"
Maintenance
".
Information:
The sensor terminates the simulation automatically after 60 minutes.
6.5.4 Additional adjustments
In this menu item, you adjust the internal clock of the sensor. There is
no adjustment for summer/winter (daylight saving) time.
After a reset, certain parameter adjustments made by the user are
reset.
The following reset functions are available:
Delivery status:
Restores the parameter settings at the time of
shipment from the factory, incl. the order-specific settings. Any user-
defined linearisation curve as well as the measured value memory are
deleted.
Basic settings:
Resets the parameter settings, incl. special param-
eters, to the default values of the respective instrument. Any pro-
grammed linearisation curve as well as the measured value memory
are deleted.
The following table shows the default values of the instrument. De-
pending on the instrument version or application, all menu items may
not be available or some may be differently assigned:
Date/Time
Reset