19
4 Mounting
WIKA Operating Instructions - Process pressure transmitter CPT-2x
1
2
3
Fig. 15: Measurement setup for process pressure measurement of gases in
pipelines
1 CPT-2x
2 Blocking valve
3 Pipeline
Keep the following in mind when setting up the measuring system:
•
Connect via a siphon
•
Do not insulate the siphon
•
Fill the siphon with water before setup
1
4
3
2
1
2
3
4
Fig. 16: Measurement setup for the process pressure measurement of gases in
pipelines
1 CPT-2x
2 Blocking valve
3 Siphon in U or circular form
4 Pipeline
A protective accumulation of water is formed through condensation
in the pipe bends. Even in applications with hot steam, a medium
temperature < 100 °C on the transmitter is ensured.
Measurement setup in
vapours