17
Figure 3-10 The percentage of ethylene propylene glycol and freezing point
Note:
the percentage composition of ethylene propylene glycol should not exceed 50%.
3)
The selfmade compound coolant is suitable to use in high temperature (over
38
℃
/100
℉
) .
The treated water works better when used in warm environment.
The treated water is a mixed water of pure water(which meet the below purity standard)
and benzotriazole with percentage of 300:1. As a corrosion inhibitor, benzotriazole is
suitable for copper cooling system included in plasma system.
4)
Water purity
Table 3-7 Specification of water purity
Specification of water purity
Conductivity
μS/cm
(25
℃
hour)
Electrical resistivity
mΩ•cm
(25
℃
hour)
NaCl content
(
Unit ppm
)
CaCO3 content
(
Unit ppm
)
Pure water
(Just for reference)
0.055
18.3
0
0
Max. purity
0.5
2
0.206
0.171
Min. purity
18
0.054
8.5
7.35
Max. purity of drinking
water
1000
0.001
495
428