Multi-Beam Safety Light Array
111
9.5.6.3 Parametrization Four Sensor Linear Muting with Sequence (LSEQ) or Time Monitoring (LTME)
• For general information on four sensor linear muting with sequence monitoring, see
for four sensor linear muting with time monitoring.
• All settings under the muting function must be carried out in one go. If the four sensor linear muting menu
item is called up again, the parameter configurations must be set again for the desired options.
• The following selection options are available for four sensor linear muting:
a) Timeout / muting duration
OSSD
RES
SIG LOW
ERROR
300 sec:
• There is a time limit on the maximum duration of an active muting
sequence. There are two values to choose from.
– 300S: Muting duration max. 300 s
– 8H: Muting duration max. 8 h
• For more information on the “muting duration” function, see
OSSD
RES
SIG LOW
ERROR
8 hours
OSSD
RES
SIG LOW
ERROR
Back
OSSD
RES
SIG LOW
ERROR
b) Direction setting
OSSD
RES
SIG LOW
ERROR
Direction A
• The “direction setting” function specifies and checks the permis-
sible activation sequence of the muting signals.
• If an object passes through the safety field in a direction other
than the one defined, the muting cycle is not initiated.
– A: unidirectional – only direction A is permitted (MS1 / MS2
before MS3 / MS4)
– B: unidirectional – only direction B is permitted (MS4 / MS3
before MS2 / MS1)
– AB: bidirectional – both directions are permitted
• For more information on the “direction setting” function, see