background image

3 of 20

WX-501-0517 • 05.22

DIP switches

Just behind the faceplate of the Click 110, on the circuit board, is a set of DIP switches. These switches are used to 

configure the Click 110 in Hardware mode. All settings, with the exception of Outstation mode and disabling fault 

latching, are also configurable via Software mode (front panel menu, or Click Supervisor). See the DIP Switches 

section of this document for more information.

Installation and wiring

Use the following steps to install and wire Click 110 devices:
1.  If you’re using hardware configuration, set all DIP switches before installing Click 110 devices (this will be 

covered in the DIP Switches section of this document).

2.  Insert the cards into the rack.
3.  Daisy-chain together all the cards you intend to use in your installation, using short RJ-11 jumper cables.
4.  Connect the first Click 110 card to the SmartSensor via a surge protector, such as the Click 200, 222, or 223, 

and a 60” RJ-11 patch cord.

For your information, this document includes the pinout for the 64-pin backplane connector on the the back of the 

Click 110. However, the pins behave differently depending on which Outstation mode the device is set to, Peek or 

Siemens (for more on Outstation mode, see the DIP Switches section of this document); the differences all relate 

to the fault outputs and whether they are normally opened or normally closed.

For this reason, there are two pinout tables on the following pages. The first is the pinout when the Click 110 is set 

to Peek; the second is when it’s set to Siemens.

Note. 

The pins that change between the two tables will be highlighted in light gray for ease of comparison.

Summary of Contents for Click 110

Page 1: ...1 21 24 1 1 1 0 25 28 1 1 1 1 29 32 S3 Channel Enable 4 5 6 7 8 Channel 0 SW Con g 1 1 1 2 1 3 1 4 S1 Bus 2 Baud Rate 5 6 7 8 Value 0 SW Con g 1 0 0 0 9600 1 0 0 1 19200 1 0 1 0 38400 1 0 1 1 57600 1...

Page 2: ...s numbered 1 4 left to right Level 1 LEDs display which menu is active These Level 1 LEDs are dual purpose each indicating both menu selection as well as a normal operation state when not in Menu mode...

Page 3: ...hain together all the cards you intend to use in your installation using short RJ 11 jumper cables 4 Connect the first Click 110 card to the SmartSensor via a surge protector such as the Click 200 222...

Page 4: ...ction B25 No connection B26 No connection B27 No connection B28 No connection B29 DC 12 24 VDC B30 No connection B31 DC common B32 Pin Description A1 Channel 1 normally closed A2 No connection A3 Chan...

Page 5: ...tion B25 No connection B26 No connection B27 No connection B28 No connection B29 DC 12 24 VDC B30 No connection B31 DC common B32 Pin Description A1 Channel 1 normally closed A2 No connection A3 Chann...

Page 6: ...ument Configuration The Click 110 can be configured in three ways DIP switches the front panel menu and Click Supervisor These three different configuration methods can configure different sets of opt...

Page 7: ...tstation mode Fault latch Each parameter except fault latch and outstation mode has a way to pick between Hardware Software modes If Software mode is selected the parameter must be configured using th...

Page 8: ...If switch 1 5 is off down Software mode is selected and Click Supervisor and the front panel menu will be able to both display and change the current setting Channel enable The next parameter that ca...

Page 9: ...output channels only four input datagram channels received from the sensor can be output by each device If you need more than four channels consider using multiple devices As shown in the table below...

Page 10: ...configuration modes Fault latch The last option that can be configured on the DIP switches is fault latching This is configured on the third DIP switch labeled S3 using switch 8 S3 8 Note This paramet...

Page 11: ...ower bank also function as activity status indicators These functions outlined in the Physical Features section of this document are only executed when the device is not in Menu mode In this case the...

Page 12: ...ase how to autobaud bus 2 Mode switch action Display State None Normal operation Press and hold Channel map menu option displayed Continue holding Autobaud menu option displayed Release Autobaud menu...

Page 13: ...ged using the DIP switches or Click Supervisor As mentioned earlier the Click 110 device receives serial datagrams from a SmartSensor These datagrams can contain many channels of detection data Becaus...

Page 14: ...buses you will select which bus to autobaud on the Level 2 LEDs An autobaud will stop data reporting on the selected port and attempt to communicate with the SmartSensor at all supported baud rates Le...

Page 15: ...default 19200 bps 38400 bps 57600 bps LED off Cancel and exit menu LED on See the earlier Navigating through the Menu and the Menu Operation Example sections for how to configure this parameter Becau...

Page 16: ...on Example sections for how to configure this parameter Because this parameter can also be set by the DIP switches you may need to ensure that the DIP switches are set to Software configuration mode i...

Page 17: ...eptions are fault latch and outstation mode which are not reset by this option Level 1 LEDs Reset to default settings Level 2 LEDs Reset to default settings LED off Cancel and exit menu LED on See the...

Page 18: ...ral tab lets you change general information about your device The tab has the following parameters see the figure and table below Note This parameter can only be configured using Click Supervisor Sett...

Page 19: ...Bus 1 Lets you change the baud rate in bps of bus 1 Baud Rate for Bus 2 Lets you change the baud rate in bps of bus 2 Input Mapping Lets you assign input datagram channels received from the sensor to...

Page 20: ...problems are detected a green circle will appear Once you have finished use the menu bar at the top of the screen to save your settings return to the Select Driver screen and more The Save menu allows...

Reviews: