background image

10 of 20

WX-501-0517 • 05.22

If switch 1 is off (down), 

Software

 mode is selected and Click Supervisor and the front panel menu will be able to 

both display and change the current setting.

Outstation Mode

Also on this switch is the outstation mode. This is configured on the third DIP switch, labeled S3, using switch 6 (S3:6).

Note. 

This parameter can only be changed using the DIP switches.

The Click 110 can be used with two brands of outstations, Peek and Siemens. Because of differences in the way 

these two operate, you need to use switch 6 on the S3 DIP switch to tell the Click 110 with which outstation it is 

going to be used.

If S3:6 is off (down), the Click 110 is set to work with a Peek brand outstation. If S3:6 is on (up), the Click 110 is set to 

work with a Siemens brand outstation.

S3: Outstation mode

6

State

Off

Peek

On

Siemens

Note. 

In Peek mode the Isolated fault output channels are N/C; in Siemens mode they are N/O. The Master Fault 

output relay is also opposite when switching between the two modes. Refer to the pinout table earlier in this 

document for more information.

Because Outstation mode can only be changed using the DIP switches (though it can be viewed elsewhere), there 

is no option for selecting 

Hardware

 or 

Software

 configuration modes.

Fault latch

The last option that can be configured on the DIP switches is fault latching. This is configured on the third DIP 

switch, labeled S3, using switch 8 (S3:8).

Note. 

This parameter can only be changed using the DIP switches.

Fault latching involves how the Click 110 reacts when the flow of data from the connected SmartSensor is 

interrupted. As mentioned in the Fail-safe Mode section above, if the Click 110 does not receive a datagram 

containing a channel that is mapped to its outputs for ten seconds, the device will enter fail-safe mode.

In fail-safe mode, all enabled outputs will assert a detection and fault condition. The master fault output will also 

assert. As long as the flow of data is reestablished within one minute, the device will exit the mode and continue 

normal operation. How the device reacts when data flow is not reestablished is determined by whether fault latch 

is enabled or disabled.

If S3:8 is on (up), fault latching is disabled. This means that if the Click 110 starts to receive data again at any point 

after the one-minute mark, the device will exit fail-safe mode and continue normal operation. If S3:8 is off (down), 

fault latching is enabled. In this case, if the fault condition has existed for more than one minute, normal mode can 

only be restored by rebooting (front panel reset switch, power cycle, or remote reset via outstation), even if the 

device has started to receive data again.

Summary of Contents for Click 110

Page 1: ...1 21 24 1 1 1 0 25 28 1 1 1 1 29 32 S3 Channel Enable 4 5 6 7 8 Channel 0 SW Con g 1 1 1 2 1 3 1 4 S1 Bus 2 Baud Rate 5 6 7 8 Value 0 SW Con g 1 0 0 0 9600 1 0 0 1 19200 1 0 1 0 38400 1 0 1 1 57600 1...

Page 2: ...s numbered 1 4 left to right Level 1 LEDs display which menu is active These Level 1 LEDs are dual purpose each indicating both menu selection as well as a normal operation state when not in Menu mode...

Page 3: ...hain together all the cards you intend to use in your installation using short RJ 11 jumper cables 4 Connect the first Click 110 card to the SmartSensor via a surge protector such as the Click 200 222...

Page 4: ...ction B25 No connection B26 No connection B27 No connection B28 No connection B29 DC 12 24 VDC B30 No connection B31 DC common B32 Pin Description A1 Channel 1 normally closed A2 No connection A3 Chan...

Page 5: ...tion B25 No connection B26 No connection B27 No connection B28 No connection B29 DC 12 24 VDC B30 No connection B31 DC common B32 Pin Description A1 Channel 1 normally closed A2 No connection A3 Chann...

Page 6: ...ument Configuration The Click 110 can be configured in three ways DIP switches the front panel menu and Click Supervisor These three different configuration methods can configure different sets of opt...

Page 7: ...tstation mode Fault latch Each parameter except fault latch and outstation mode has a way to pick between Hardware Software modes If Software mode is selected the parameter must be configured using th...

Page 8: ...If switch 1 5 is off down Software mode is selected and Click Supervisor and the front panel menu will be able to both display and change the current setting Channel enable The next parameter that ca...

Page 9: ...output channels only four input datagram channels received from the sensor can be output by each device If you need more than four channels consider using multiple devices As shown in the table below...

Page 10: ...configuration modes Fault latch The last option that can be configured on the DIP switches is fault latching This is configured on the third DIP switch labeled S3 using switch 8 S3 8 Note This paramet...

Page 11: ...ower bank also function as activity status indicators These functions outlined in the Physical Features section of this document are only executed when the device is not in Menu mode In this case the...

Page 12: ...ase how to autobaud bus 2 Mode switch action Display State None Normal operation Press and hold Channel map menu option displayed Continue holding Autobaud menu option displayed Release Autobaud menu...

Page 13: ...ged using the DIP switches or Click Supervisor As mentioned earlier the Click 110 device receives serial datagrams from a SmartSensor These datagrams can contain many channels of detection data Becaus...

Page 14: ...buses you will select which bus to autobaud on the Level 2 LEDs An autobaud will stop data reporting on the selected port and attempt to communicate with the SmartSensor at all supported baud rates Le...

Page 15: ...default 19200 bps 38400 bps 57600 bps LED off Cancel and exit menu LED on See the earlier Navigating through the Menu and the Menu Operation Example sections for how to configure this parameter Becau...

Page 16: ...on Example sections for how to configure this parameter Because this parameter can also be set by the DIP switches you may need to ensure that the DIP switches are set to Software configuration mode i...

Page 17: ...eptions are fault latch and outstation mode which are not reset by this option Level 1 LEDs Reset to default settings Level 2 LEDs Reset to default settings LED off Cancel and exit menu LED on See the...

Page 18: ...ral tab lets you change general information about your device The tab has the following parameters see the figure and table below Note This parameter can only be configured using Click Supervisor Sett...

Page 19: ...Bus 1 Lets you change the baud rate in bps of bus 1 Baud Rate for Bus 2 Lets you change the baud rate in bps of bus 2 Input Mapping Lets you assign input datagram channels received from the sensor to...

Page 20: ...problems are detected a green circle will appear Once you have finished use the menu bar at the top of the screen to save your settings return to the Select Driver screen and more The Save menu allows...

Reviews: