background image

17 of 20

WX-501-0517 • 05.22

After you have viewed the fault latch configuration, press and release the 

Mode

 

Switch

 to exit.

Outstation mode

The next option you come across in the front panel menu is outstation mode. Like fault latch, this is read-only in 

the front panel menu; you can use it to view which kind outstation the device is set to use, Peek or Siemens. To 

modify this setting, use the DIP switches (see the DIP Switches section for more information).

Level 1 LEDs

  

  

  

Outstation mode

Level 2 LEDs

Peek Outstation Support

  

LED off

  

  

  

Siemens Outstation Support

  

LED on

See the earlier Navigating through the Menu and the Menu Operation Example sections for how to view this parameter.

After you have viewed the outstation mode configuration, press and release the 

Mode

 

Switch

 to exit.

Reset to default settings

The final option that comes up in the menu is Reset to Default Settings. To select this function, release the 

Mode

 

Switch

 when the red LED starts flashing.

Note. 

This parameter can only be configured using the DIP switches.

This function will restore all configuration settings to factory defaults, even those parameters not configured using 

the front panel menu: baud rate, channel map, channel enable, description field, location field, and device ID. (The 

exceptions are fault latch and outstation mode, which are not reset by this option.)

Level 1 LEDs

  

  

  

Reset to default settings

Level 2 LEDs

Reset to default settings

  

LED off

  

  

  

Cancel and exit menu

  

LED on

See the earlier Navigating through the Menu and the Menu Operation Example sections for how to view this 

parameter.

After the Click 110 has reset to factory defaults, it will check the DIP switches; if any of them are set to 

Hardware

 

mode, it will apply those settings to the parameter in question. If resetting to factory defaults doesn’t change 

certain settings the way you expected it to, check the DIP switches to see if they are causing settings to be 

changed to something other than the default.

Click Supervisor

Click Supervisor is the only way to configure non-data path type parameters such as the description, location, and 

device ID. See the knowledge base article 

0514 Installing and Using Click Supervisor

 for instructions on how to 

download and install Click Supervisor and how to connect to your device using the software.

Note. 

Some of the parameters mentioned below can only be configured in Click Supervisor. Others can be 

configured by the front panel menu and/or the DIP switches. In the case of the DIP switches, if that parameter is 

set to 

Hardware

 mode, it will be grayed out in Click Supervisor, meaning you can view but not change the setting. 

If you would like to set it using Click Supervisor, you will have to flip those switches on the device.

Summary of Contents for Click 110

Page 1: ...1 21 24 1 1 1 0 25 28 1 1 1 1 29 32 S3 Channel Enable 4 5 6 7 8 Channel 0 SW Con g 1 1 1 2 1 3 1 4 S1 Bus 2 Baud Rate 5 6 7 8 Value 0 SW Con g 1 0 0 0 9600 1 0 0 1 19200 1 0 1 0 38400 1 0 1 1 57600 1...

Page 2: ...s numbered 1 4 left to right Level 1 LEDs display which menu is active These Level 1 LEDs are dual purpose each indicating both menu selection as well as a normal operation state when not in Menu mode...

Page 3: ...hain together all the cards you intend to use in your installation using short RJ 11 jumper cables 4 Connect the first Click 110 card to the SmartSensor via a surge protector such as the Click 200 222...

Page 4: ...ction B25 No connection B26 No connection B27 No connection B28 No connection B29 DC 12 24 VDC B30 No connection B31 DC common B32 Pin Description A1 Channel 1 normally closed A2 No connection A3 Chan...

Page 5: ...tion B25 No connection B26 No connection B27 No connection B28 No connection B29 DC 12 24 VDC B30 No connection B31 DC common B32 Pin Description A1 Channel 1 normally closed A2 No connection A3 Chann...

Page 6: ...ument Configuration The Click 110 can be configured in three ways DIP switches the front panel menu and Click Supervisor These three different configuration methods can configure different sets of opt...

Page 7: ...tstation mode Fault latch Each parameter except fault latch and outstation mode has a way to pick between Hardware Software modes If Software mode is selected the parameter must be configured using th...

Page 8: ...If switch 1 5 is off down Software mode is selected and Click Supervisor and the front panel menu will be able to both display and change the current setting Channel enable The next parameter that ca...

Page 9: ...output channels only four input datagram channels received from the sensor can be output by each device If you need more than four channels consider using multiple devices As shown in the table below...

Page 10: ...configuration modes Fault latch The last option that can be configured on the DIP switches is fault latching This is configured on the third DIP switch labeled S3 using switch 8 S3 8 Note This paramet...

Page 11: ...ower bank also function as activity status indicators These functions outlined in the Physical Features section of this document are only executed when the device is not in Menu mode In this case the...

Page 12: ...ase how to autobaud bus 2 Mode switch action Display State None Normal operation Press and hold Channel map menu option displayed Continue holding Autobaud menu option displayed Release Autobaud menu...

Page 13: ...ged using the DIP switches or Click Supervisor As mentioned earlier the Click 110 device receives serial datagrams from a SmartSensor These datagrams can contain many channels of detection data Becaus...

Page 14: ...buses you will select which bus to autobaud on the Level 2 LEDs An autobaud will stop data reporting on the selected port and attempt to communicate with the SmartSensor at all supported baud rates Le...

Page 15: ...default 19200 bps 38400 bps 57600 bps LED off Cancel and exit menu LED on See the earlier Navigating through the Menu and the Menu Operation Example sections for how to configure this parameter Becau...

Page 16: ...on Example sections for how to configure this parameter Because this parameter can also be set by the DIP switches you may need to ensure that the DIP switches are set to Software configuration mode i...

Page 17: ...eptions are fault latch and outstation mode which are not reset by this option Level 1 LEDs Reset to default settings Level 2 LEDs Reset to default settings LED off Cancel and exit menu LED on See the...

Page 18: ...ral tab lets you change general information about your device The tab has the following parameters see the figure and table below Note This parameter can only be configured using Click Supervisor Sett...

Page 19: ...Bus 1 Lets you change the baud rate in bps of bus 1 Baud Rate for Bus 2 Lets you change the baud rate in bps of bus 2 Input Mapping Lets you assign input datagram channels received from the sensor to...

Page 20: ...problems are detected a green circle will appear Once you have finished use the menu bar at the top of the screen to save your settings return to the Select Driver screen and more The Save menu allows...

Reviews: