TROUBLESHOOTING
SERIES :
114 - 116
Fault:
Problem Cause:
Action:
Elevator Will Not Accept a
Call
Open safety
Check for required inputs
Door Lock cycle count
Door must be cycled after four calls or the
system will stop functioning
Open gate and open door
Does Not Slow Down
PLC count is incorrect
Check for DZ input when elevator is running
Improper magnet placement
Check magnet placement
Travels Past Floor then
Relevels
Leveling speed is too fast
Adjust leveling speed
HSV Relay is welded
Will Not Travel Down
Pipe rupture valve is out of
adjustment
Check pipe rupture valve and adjust
Check pressure gage to determine if pipe
rupture is working
Elevator stops just outside
of the door zone while leav-
ing the fl oor landing
(EMI-III) Missing jumper from
DC to DL
Add the 2 pole jumper in DC and DL in
controller
Faulty EMI
Replace or adjust EMI
(EMI-IV) Door Locked Circuit
Open
Verify wiring and alignment of EMI
If the unit can run with the
door open with an EMI-IV
and GAL interlocks
Verify the door lock and door
closed aren’t tied together
Verify EMI-IV interlock wiring
Remove the 2 pole jumper from DC and DL
in the controller
Page 64