DO NOT RUN ELEVATOR WITHOUT THE FINAL LIMIT SWITCH INSTALLED!
Screw
FINAL LIMIT
INSTALLATION
SERIES :
114, 116
3.
3, 6
4
Position the top fi nal limit switch
assembly in the desired location at the
top of the elevator hoistway. Only the
switch arm from the assembly must
make contact with the elevator and shall
fully actuate before the elevator hits any
obstruction. (i.e., ceiling, electrical and/
or mechanical part, etc.)
Fasten the fi nal limit switch assembly
to the hoistway with the appropriate
hardware.
Loosen the screw and open cover. Verify
the normally closed contacts with a
multi-meter.
Wire to the previously verifi ed normally
closed terminals. All wiring must meet
N.E.C. and local codes.
Note:
Do not over tighten
terminals. Terminals should be
torqued to 7lb-in max.
Verify the operation of the fi nal limit
switch.
Replace cover and refasten screw.
Adjust as necessary, the fi nal limit switch
assembly may move or need adjustment
after the elevator car is installed.
2.
6.
1.
5.
4.
Wire to Terminals TF1and TF2
ANTI-
STATIC
ALERT
CRUSH
HAZARD
CUTTING
HAZARD
HAZARD
CRUSH
ELECTRIC
HAZARD
FALLING
HAZARD
PINCH
HAZARD
Torque the
Normally
Closed
Terminals
to 7lb-in max.
7.
Note:
Verify the switch actuates and
disconnects power to the driving
machine before the elevator is at its
max extent or strikes any obstruction.
Page 18