Innovation - Edge [i] Installation, Operation, Maintenance Manual
CHAPTER 8
– WATER HEATER MANAGEMENT
OMM-0143_A
• GF
-216
•
9/6/2019
Technical Support
•
(800) 526-0288
•
Mon-Fri, 8 am - 5 pm EST Page 122 of 170
TABLE 8-6g: Operating Controls
→
Lead/Lag Control Parameters
Menu Item Display
Available Choices or Limits
Default
Minimum
Maximum
Lead/Lag Setting
Run Hours, Unit Size,
Select Lead/Lag
Select Lead/Lag
Determines how the Lead and Lag units will be selected.
Run Hours
25
225
72
Specify the number of hours after which the Lead unit is rotated.
Lead Unit
0
16
0
Specify the address of the Lead unit.
Lag Unit
0
16
16
Specify the address of the Lag unit.
Figure 8.6-7: Operating Controls: Lead/Lag Control Screen
8.7 WHM HARDWARE INSTALLATION & SET-UP
INSTRUCTIONS
The following sections provide the basic installation and set-up instructions for implementing a
Water Heater Management System (WHM) to control up to 16 AERCO Innovation Water
Heaters. Some of the descriptions and procedures included in Chapter 2 are repeated here to
avoid unnecessary referencing.