Innovation - Edge [i] Installation, Operation, Maintenance Manual
CHAPTER 3
– OPERATION
OMM-0143_A
• GF
-216
•
9/6/2019
Technical Support
•
(800) 526-0288
•
Mon-Fri, 8 am - 5 pm EST Page 47 of 170
Off Delay
Numeric Entry
Specifies the amount of time full shut down will be
delayed (
Slow Shutdown
=
Enabled
).
Off Delay Threshold
Numeric Entry
The threshold fire rate above which
Slow Shutdown
will
take effect (
Slow Shutdown
=
Enabled
).
Shutoff Delay Temp
Numeric Entry
The temperature above setpoint the unit may rise to
during delay shutdown (0 to 25°F).
Demand Offset
Numeric Entry
Offset temperature from setpoint before a unit may come
online (0 to 25°F).
Main Menu
→
Advanced Setup
→
WHM Cascade
→
Operating Controls
→
Valve Configuration
Select Output
Read Only
Displays
Standard Setup
.
Output Signal Type
Toggle
Select the output signal type of the selected output:
Current
or
Voltage
.
Control Mode
Read Only
Displays
On/Off
.
Valve Feedback
Enable/Disable
Choose
Enabled
or
Disabled
.
Valve Feedback Status
Read Only
Displays the selected valve’s current status (
Valve
Feedback
=
Enabled
).
Main Menu
→
Advanced Setup
→
WHM Cascade
→
Operating Controls
→
Lead/Lag
Lead/Lag Setting
Select
Select:
Run Hours
,
Unit Size
or
Select Lead Lag
.
Hours
Numeric Entry
The number of hours after which the Lead unit is rotated
(25
– 225,
Lead/Lag Setting
=
Run Hours
)
Lead Unit
Numeric Entry
Specify the address of the Lead unit (0 to 127,
(
Lead/Lag Setting
=
Select Lead Lag
).
Lag Unit
Numeric Entry
Specify the address of the Lag unit (0 to 127,
Lead/Lag
Setting
=
Select Lead Lag
).
3.3.4.3
Main Menu
→
Advanced Setup
→
Com & Network
Main Menu
→
Advanced Setup
→
Comm & Network
→
BAS
BAS
Select
To enable communication with a BAS, select
Off
or
Modbus TCP
.
Communication Address
Numeric Entry
Specify the network address of the Edge Controller on the
BAS network (0
– 127,
BAS
=
Modbus TCP
).
Local IP Address
Read Only
Displays the local IP address of the Edge Controller (
BAS
=
Modbus TCP
).
Status
Read Only
Displays the status of BAS communications.
BAS Temp Format
Toggle
Choose:
Fahrenheit
or
Celsius
(
BAS
=
Modbus TCP
)
Security
Enable/Disable
Set to
Enabled
to enable BAS security (
BAS
=
Modbus
TCP
).
BAS IP
Numeric Entry
Specifies the IP address of the BAS server
(
Security
=
Enabled
).
BAC MAC
Numeric Entry
Specifies the MAC address of the BAS server
(
Security
=
Enabled
).
Main Menu
→
Advanced Setup
→
Comm & Network
→
onAER
onAER Mode
Select
To enable onAER, select the communication method:
Ethernet
,
Wi-Fi
or
Wiznet
(for units where the Edge
Controller replaced a C-More).
Unit Upload Time
Numeric Entry
Determines how frequently unit data is uploaded to the
server (30 to 9999 sec.).
Cascade Upload Time
Numeric Entry
Determines how cascade data is uploaded to the server
(60 to 9999 sec.).
Status
Read Only
The communication interface status.
Main Menu
→
Advanced Setup
→
Comm & Network
→
Ethernet
DHCP
Enable/Disable
Enables/disables
DHCP (Dynamic Host Configuration
Protocol).
IP Address
Numeric Entry
The static IP address of the unit
(
DHCP
=
Disabled
).