Innovation - Edge [i] Installation, Operation, Maintenance Manual
CHAPTER 3
– OPERATION
OMM-0143_A
• GF
-216
•
9/6/2019
Technical Support
•
(800) 526-0288
•
Mon-Fri, 8 am - 5 pm EST Page 45 of 170
Power Reset
Toggle
Choose if power fault reset mode,
Manual
or
Automatic
.
Water Temp Reset
Toggle
Choose water temperature fault reset mode,
Manual
or
Automatic
.
Gas Pressure Reset
Toggle
Choose if gas pressure fault reset mode,
Manual
or
Automatic
.
Main Menu
→
Advanced Setup
→
Unit
→
Freeze Protection
Freeze Protection
Enable/Disable
Enables/disables Freeze Protection functionality.
Pump On Temperature
Numeric Entry
If enabled, ambient temperature below this value triggers
system pump to start (
Freeze Protection
=
Enabled
).
Unit On Temperature
Numeric Entry
Ambient temperature below this value triggers the unit to
fire (
Freeze Protection
=
Enabled
).
Stop Temperature
Numeric Entry
Ambient temperature above this value returns system to
normal operation (
Freeze Protection
=
Enabled
).
Main Menu
→
Advanced Setup
→
Unit
→
Unit Application Configuration
Unit Application
Select
Select unit’s application:
DHW
Operating Mode
Toggle
Choose either
Constant
or
Remote Setpoint
.
Setpoint
Numeric Entry
Sets the unit’s setpoint (
Operating Mode = Constant
Setpoint
).
Setpoint Low Limit
Numeric Entry
Sets the minimum setpoint.
Setpoint High Limit
Numeric Entry
Sets the maximum setpoint.
Remote Signal
Select
Select the source of the (
Operating Mode = Remote
Setpoint
).
Unit Address
Toggle
Specifies the unit’s Modbus address (
Operating Mode =
Remote Setpoint, Remote Signal = Network)
).
Cascade Baud Rate
Numeric Entry
Specifies Modbus baud rate (
Operating Mode =
Remote Setpoint
,
Remote Signal = Network
).
Main Menu
→
Advanced Setup
→
Unit
→
Maintenance
12 Month Maintenance
Complete?
Yes/No
Specifies 12 Month Maintenance completed.
Fire Side Inspection
Yes/No
Specifies Fire Side Inspection completed.
Optical Burner Inspection
Yes/No
Specifies Optical Burner Inspection completed
Water Side Inspection
Yes/No
Specifies Water Side Inspection completed.
CSD-1 Safety Device
Inspection
Yes/No
Specifies CSD-1 Safety Device inspection completed.
Combustion Calibration Check
Yes/No
Specifies Combustion Calibration Check completed.
3.3.4.2
Main Menu
→
Advanced Setup
→
WHM Cascade
Main Menu
→
Advanced Setup
→
WHM Cascade
→
Cascade Configuration
WHM Unit Mode
Select
Specifies Unit Mode:
Off
,
Client
,
Manager
.
Auto-Manager Transfer
Enable/Disable
Allows WHM Manger functionality to be transferred to
another unit if the WHM Manger malfunctions (
WHM
Unit Mode
=
WHM Manager
).
Auto-Manager Timer
Numeric Entry
Specifies duration of WHM Manger malfunction that
triggers
Auto-Manager Transfer
(10 to 120,
WHM Unit
Mode
=
WHM Manager
).
Auto-Manager Addr
Read Only
The address of the WHM Manger (0 to 16,
WHM Unit
Mode
=
WHM Manager
).
Backup Manager Addr
Numeric Entry
The address of the unit designated as the Backup WHM
Manger (0 to 16) (
WHM Unit Mode
=
WHM Manager
).
Main Menu
→
Advanced Setup
→
WHM Cascade
→
Cascade Communication
Unit Address
Numeric Entry
The unit’s address in the WHM cascade.
Min Address
Numeric Entry
The minimum address in the WHM cascade (1 to 16,
WHM Unit Mode
=
WHM Manager
).