HEAT PUMP WATER HEATER

SAHP 130 / 200 / 300

INSTALLATION AND 

MAINTENANCE INSTRUCTIONS

Summary of Contents for 130

Page 1: ...V3 June 2021US SD667052 HEAT PUMP WATER HEATER SAHP 130 200 300 INSTALLATION AND MAINTENANCE INSTRUCTIONS...

Page 2: ...TEM SECTION 5 REFRIGERATION INSTALLATION OF THE SYSTEM SECTION 6 ELECTRICAL INSTALLATION OF THE SYSTEM SECTION 7 TESTING AND COMMISSIONING SECTION 8 INSPECTION AND MAINTENANCE SECTION 9 USING THE CONT...

Page 3: ...nsibility of the installer to ensure the installation complies with all relevant local and national standards and regulations 1 2 Each component of the SAHP is supplied complete with its own instructi...

Page 4: ...ressure for one hour Systems containing plastic pipework should be pressure tested in accordance with the pipe manufacturers instructions It is also recommended that the existing system be pressure te...

Page 5: ...ransportation 2 8 If transporting in the horizontal orientation ensure the unit is laid down on it s left hand side so that the left hand side is facing the ground Failure to do so may cause permanent...

Page 6: ...inner cylinder which heats the water inside the cylinder The product iV V V i v i ivwV i i v Vi With these features the SAHP is designed to have a long trouble free life 3 3 The SAHP has integral saf...

Page 7: ...x w x d RXEOH SDQHO ZHLJKW EV RXEOH SDQHO GLPHQVLRQV K Z G panel input output XEULFDQW LQ WKH FRPSUHVVRU Sound Power Level 5 D D OREDO DUPLQJ SRWHQWLDO 3 8 SAHP 300 79 2580 6800 Typically 600 4 5 220...

Page 8: ...hot and cold water requirements of the property and user are ascertained before the installation of the SAHP 4 4 The minimum incoming cold water mains inlet requirements for the i i i x 1 i i y i 4 5...

Page 9: ...S A B C D E F G H I J K L M N O P Q R S Evaporator panel SAHP Hot water outlet Pressure temperature relief valve Dual thermostat Sensor pocket RLOHU RZ Immersion heater Boiler return Cold water in Dr...

Page 10: ...here necessary 4 13 NOTE We highly recommend installing a thermostatic mixing valve in system where the set point temperature of either the heat pump or any heat sources connected to the boiler coil a...

Page 11: ...included two port motorised zone i Li i i y Liv i i V i 4 19 i V i i v i Li w i V the latest version of relevant local and national standards 4 20 iv i w i i i i i i i i i i i 43 5psi This is the same...

Page 12: ...an be located facing any aspect On either an exterior wall or pitched roof If the panel is installed v Li w i i v kits in accordance with relevant local and national standards 5 3 The evaperator panel...

Page 13: ...secure the evaperater panel to a wall as show in w i i w V i i i i i NOTE Ensure that the SAHP is connected to the evaperator SDQHO FRUUHFWO DV VKRZQ LQ JXUH IDLOXUH WR GR VR FDQ UHVXOW in compressor...

Page 14: ...eration oil on the thread of the n y i V iV Liv i i i y i 5 8 Pipework Installation All refrigeration pipework should be installed in accordance with ISO 5149 5 9 The SAHP is factory pre charged with...

Page 15: ...speed recovery time by up to 10 this is in addition to any gas added as per 5 10 5 12 The refrigeration circuit shall be designed with as few bends as possible with no single bend to exceed a 90O ben...

Page 16: ...iquid inlet and the SAHP suction side is connected to the Panel gas inlet NOTE Do not loosen or open service ports until all connections are made and the system has been fully leak checked and vacuume...

Page 17: ...y completed and i i v i Lii V w i i i V be vented The vacuum pump must be connected into the service port to begin vacuuming evacuating the system Vaccum the system to 0 5 torr 500 microns for a minim...

Page 18: ...electrical consumer panel to provide 220 240V power supply to the SAHP Be sure to clearly label the wires 220 240V on each end for safety NOTE In areas with 4 conductor L1 L2 N and G wiring connect L...

Page 19: ...1 0mm CONDUCTOR SIZE ETC CIRCUIT B BR SWITCH B 1 0 FRONT TERMINALS REAR TERMINALS KLIXON CAPACITOR BR 1 0 R 1 0 G Y 1 5 SWITCH HEATER TERMINALS CAPACITOR G Y 1 5 BR 1 5 B 1 5 IMMERSION HEATER L N E MA...

Page 20: ...7 6 10 To connect the SAHP to a PV inverter a 2 conductor wire is required There is no maximum or minimum distance requirements of this 2 conductor wire The cable will be carrying a voltage free sign...

Page 21: ...w keys until 140 is displayed on the controller Press P Hold U arrow key for 5 seconds SP is displayed Press arrow keys until rE is displayed Press P Press arrow keys until r d is displayed Press P Pr...

Page 22: ...e minute Press P d xx is shown d stands for day of the week d 01 Monday d 02 Tuesday etc Select the appropriate day 3UHVV 3 WR FRQ UP c CL is shown Select c dt scrolling with the arrow down c dt stand...

Page 23: ...ce it falls to 130 F or 10 F lower than programmed temperature e Standard Mode also incorporates an Anti legionella cycle this is is actuated automatically once a week every Monday between 05 00 to 07...

Page 24: ...ife of the compressor c Leave the system running for a minimum of 30 minutes and check 1 The sight glass to make sure it is clear and dry A fully functioning properly charged system should show no bub...

Page 25: ...In areas subject to freezing protection has been provided There is no hot water leaking from the water supply hot water supply pipes and temperature and pressure relief valve s Pipework is installed...

Page 26: ...ndensation insulation excluding L y i i i i present within the insulation If a heat source has been connected to the boiler coil a dual thermostat and motorized isolation valve have been installed and...

Page 27: ...and D2 is carrying the water away adequately If not check for any potential blockages and clear them where necessary WARNING THE DISCHARGING WATER MAY BE HOT c Check that the factory installed immersi...

Page 28: ...SCRIPTION P BUTTON UP BUTTON DOWN BUTTON ACTION Press to show SP program mode to change operating temperature of the compressor Increases the temperature Decreases the temperature COMMENTS The tempera...

Page 29: ...playing the set point of the temperature of the cylinder SP current set point value will be shown alternately Set the new maximum temperature value for the cylinder by pressing the up or down button O...

Page 30: ...ON Check the power supply Check that the power switch is on Please check the gas through the sight glass Verify the cleanliness of the plumbing circuit Check the pressure switches function properly Li...

Page 31: ...tion Refrigerant Leak or charge SOLUTION Check the temperature set point on screen Check the right placement of the temperature sensor inside the cylinder Check the proper insulation of the plumbing c...

Page 32: ...lation and replacement No guarantee of performance can be given if non Manufacturer approved parts are used REPLACEMENT OF PARTS 3 1 4 2 240V 1 5 Kw immersion heater 1 3 4 thread Unvented cold feed co...

Page 33: ...covery equipment for other refrigerants may damage the equipment or the unit b When carrying out the refrigerant collection on site unit operation is prohibited ensure the unit is turned off at the fu...

Page 34: ...rminal blocks located at the front of the unit Ensure to appropriately mark these cables for reconnection later on e Lift and remove the existing heat pump plate Ensure to take care when removing the...

Page 35: ...ewly brazed refrigeration connections with a leak detector If during the 45 minutes of monitoring the pressure in the system iV i i L i i i y i V iV restart the test Repeat if necessary until pressure...

Page 36: ...and evaporator If the pipework i i i i v v x Li i i n additionally R134a 513a 3 4 Ibs maximum refrigeration quantity within the system d When charging the differential in pressure between the R134a 51...

Page 37: ...f the V v i V w i i i v i V and not with the installation design or operation then contact should be made with SAHP SAHP is not responsible for shipping costs asso ciated with warranty returns By this...

Page 38: ...ll bond evaporator panel is guaranteed for 10 years from the date of purchase The guarantee shall only be valid subject to the following conditions Its installation shall be carried out in accordance...

Page 39: ...ith values exceeding ceilings set by legislation Absence of security group in the inlet system according to the legislation System malfunction arising from improper installation of the hydraulic circu...

Page 40: ...CE RECORD Date of visit Engineer Name Job Role Company Name Telephone Number Comments Signature Date of visit Engineer Name Job Role Company Name Telephone Number Comments Signature Date of visit Engi...

Page 41: ...that install maintain or dispose of equipment share responsibility for trying to stop leaks with the operators of equipment They must check all equipment for leaks RECOVER F GASES WHEN DISPOSING OF EQ...