Innovation - Edge [i] Installation, Operation, Maintenance Manual
CHAPTER 3
– OPERATION
OMM-0143_A
• GF
-216
•
9/6/2019
Technical Support
•
(800) 526-0288
•
Mon-Fri, 8 am - 5 pm EST Page 40 of 170
3.3.2 Calibration Menu
The Calibration menu contains the following sections and parameters:
Main Menu
→
Calibration
→
Combustion Calibration
NOx Requirement
Select
Select the unit’s NOx requirement:
None
,
<= 20
or
<= 9
PPM
.
Valve Position - Target
Read Only
The unit’s target Valve Position.
Valve Position - Reading
Read Only
The unit’s actual Valve Position.
Blower Voltage - Target
Read Only
Target blower voltage for current Valve Position.
Blower Voltage - Reading
Read Only
The unit’s actual blower voltage.
O2% - Target
Read Only
The unit’s target O
2
% in the exhaust.
O2% - Reading
Numeric Entry
The unit’s actual O
2
% in the exhaust.
CO - Target
Read Only
The target CO amount in the exhaust, in ppm.
CO - Reading
Numeric Entry
The actual CO amount in the exhaust, in ppm.
NOx - Target
Read Only
The target NOx amount in the exhaust, in ppm
NOx - Reading
Numeric Entry
The actual NOx amount in the exhaust, in ppm.
Flame Strength - Reading
Numeric Entry
The unit’s Flame Strength, from Multimeter
Blower Speed - Target
Read Only
Target blower speed for current Valve Position.
Blower Speed - Reading
Read Only
Actual blower speed for current Valve Position.
Air Temperature - Reading
Read Only
The current air temperature.
Downstream Gas pressure
Numeric Entry
Appears only when fire rate = 100%.
Blower Voltage
Adjust
Adjust as needed to match targets to actual readings.
3.3.2.1
Main Menu
→
Calibration
→
Input/Output
Main Menu
→
Calibration
→
Input/Output
→
Temperature Sensors
Sensor
Select
Select:
Feed Forward
,
Exhaust
,
Outside Temp
,
Air
Inlet
,
Lower Inlet
,
Outlet
.
Offset
Numeric Entry
Optional offset applied to current Sensor
Current Reading
Read Only
Current sensor’s current reading. (Flow In Adj & Flow
Rate removed ) .
Main Menu
→
Calibration
→
Input/Output
→
Analog Inputs
Analog Name
Select
Select:
Flow
or
Remote Analog In
.
Offset
Numeric Entry
A correction value to selected input, if needed.
Current Reading
Read Only
Current reading of selected input.
Main Menu
→
Calibration
→
Input/Output
→
Analog Outputs
Analog Name
Read Only
The name
Analog Output
.
Level
Numeric Entry
Set the output’s level (0.00 to 20.00 mA)
Offset
Numeric Entry
A correction value to the analog output, if needed.
3.3.2.2
Main Menu
→
Calibration
→
Subsystems
Main Menu
→
Calibration
→
Subsystems
→
Air Fuel Valve
Valve Position
Manual Adjust
Set to desired Valve Position.
A/F Sensitivity
Numeric Entry
Set Air/Fuel Valve sensitivity (1% to 5%)
Main Menu
→
Calibration
→
Subsystems
→
Spark Monitor