INSTALLER MENU FUNCTIONS
Table 5. SmartDC Controller - Installer Menu Functions
Table 5. SmartDC Controller - Installer Menu Functions
Ref.
No�
Installer Menu
Setting Options
(
Bold
= Factory Settings)
Menu Tasks and Explanations
Associated
DC Controller
Connections
Display
5
WT 0
GATE WEIGHT (LB)
0 = Gate disabled
1, 2, 3, or 4 Gate weight
selections appear in
pounds.1 = 0 to 300 lbs.
2 = 301 to 600lbs.
3 = 601 to 800lbs.
4 = 800 to 1300lbs.
Select the gate’s weight range in pounds.
The installer must designate the gate’s
weight before the operator will function. See
Configuring the Setup Menu
. Designating
the correct gate weight allows the operator
to determine the appropriate acceleration
and deceleration rates.
(N/A)
6
LN 0
GATE LENGTH (FT)
0 = Gate disabled
1 = 0 to 8 feet
2 = 8 to 12 feet
3 = 12 to 15 feet
4 = 16 to 20 feet –
DO
NOT USE
; setting of 15
feet is the FoldSmart
maximum.
Select the gate’s length in feet. The installer
must designate the gate’s length before the
operator will function. See
Configuring the
Setup Menu
. Designating the correct gate
length allows the operator to determine the
appropriate acceleration and deceleration
rates.
(N/A)
7
OS 5
OPEN SPEED
5
1 through 10
1 = slowest speed
10 = fastest speed
The range 1 through 10 varies the speed
of the motor and the gate opening speed
increases as you go up the number scale.
A setting of 1 slows the gate travel to
approximately 15 seconds. A setting of 10
speeds up gate travel to approximately 10
seconds. See
(N/A)
8
CS 5
CLOSE SPEED
5
1 through 10
1 = slowest speed
10 = fastest speed
The range 1 through 10 varies the speed
of the motor and the gate closing speed
increases as you go up the number scale.
A setting of 1 slows the gate travel to
approximately 15 seconds. A setting of 10
speeds up gate travel to approximately 10
seconds. See
Adjusting the Gate Speed.
(N/A)
9
FD 0 (OFF)
LOAD FACTORY DEFAULTS
0 = custom user settings
1 = reload factory
default settings
Globally restores all menu settings back
to new operator status. Select setting 1 to
return the operator to factory defaults.
Note: If factory defaults are restored,
the UL usage class, handing, gate weight
and length and any other modified menu
settings will need to be reprogrammed.
(N/A)
Summary of Contents for FOLDSMART
Page 36: ...36 wallaceperimetersecurity com Phone 866 300 1110 FOLDSMART GATE INSTALLATION ...
Page 38: ...38 wallaceperimetersecurity com Phone 866 300 1110 FOLDSMART GATE INSTALLATION ...
Page 146: ......
Page 147: ...FoldSmart XT Drawings Generic Site Layout and Options ...
Page 148: ......
Page 149: ......
Page 150: ......
Page 151: ......
Page 152: ......
Page 153: ......
Page 154: ......
Page 155: ......
Page 156: ......
Page 157: ......
Page 158: ......
Page 160: ......