WAGO-I/O-SYSTEM 750 XTR
Fieldbus Communication 199
750-352/040-000 FC ETHERNET G3 XTR
Manual
Version 1.3.0
Table 184: Static assembly instances – Instance 108 (6C
hex
)
Attribute ID Acces
s
Name
Data type
Description
Default value
3
Get
Data
ARRAY of BYTE
Reference of the process
image: only digital input data
-
Instance 109 (6D
hex
)
This assembly instance contains analog input data.
Table 185: Static assembly instances – Instance 109 (6C
hex
)
Attribute ID Acces
s
Name
Data type
Description
Default value
3
Get
Data
ARRAY of BYTE
Reference of the process
image: only analog input data
-
Pos: 96.5 /Serie 750 (WAGO-I/O-SYST EM)/F unktionsbeschr eibung/Fel dbuskommuni kati on/EtherNetIP/Instanz 198, 199, C ommon ser vice @ 3\mod_1233753006078_21.docx @ 27064 @ @ 1
Instance 1 (01 hex) "Configuration"
This Instance can optionally be used in the "Configuration Path" of a connection if
the associated connection originator (for example the master) requires the
specification of a "Configuration Path". The data length of this Instance is always
zero.
Instance 198 (C6
hex
) “Input Only”
This instance is used to establish a connection when no outputs are to be
addressed or when inputs, which are already being used in an exclusive owner
connection, are to be interrogated. The data length of this instance is always
zero.
This instance can only be used in the “consumed path” (seen from the slave
device).
Instance 199 (C7
hex
) “Listen only”
This instance is used to establish a connection based on an existing exclusive
owner connection. The new connection also has the same transmission
parameters as the exclusive owner connection. When the exclusive owner
connection is cleared, this connection, too, is automatically cleared. The data
length of this instance is always zero.
This instance can only be used in the “consumed path” (from the point of view of
the slave device).