222 Fieldbus Communication
WAGO-I/O-SYSTEM 750 XTR
750-352/040-000 FC ETHERNET G3 XTR
Manual
Version 1.3.0
Instance 766 ... 1020 (Analog output value 766 up to 1020)
Table 247: Analog Output Point Extended 3 (74
hex
) – Instance 766...1020
Attribute ID Access Name
Data type Description
Default
value
1
Get
AopObj_Value ARRAY of
BYTE
Analog Output
-
2
Get
AopObj_Value_
Length
USINT
Length of the output data
AopObj_Value (in byte)
-
Common Services
Table 248: Analog Output Point Extended 3 (74
hex
) – Common service
Service
code
Service available
Service name
Description
Class Instance
0E
hex
Yes
Yes
Get_Attribute_Single Supplies contents of the appropriate
attribute
10
hex
No
Yes
Set_Attribute_Single Modifies an attribute value
11.3.5.29 Module Configuration (80
hex
)
Instance 0 (Class Attributes)
Table 249: Module Configuration (80
hex
) – Class
Attribute ID Access Name
Data type Description
Default
value
1
Get
Revision
UINT
Revision of this object
1 (0x0001)
2
Get
Max Instance
UINT
Max. number of instances
-
Instance 1 … 255 (Clamp 0 up to 254)
Table 250: Module Configuration (80
hex
) – Instance 1...255
Attribute ID Access Name
Data type Description
Default
value
1
Get
ModulDescription
WORD
Description of connected modules
(module 0 = coupler/controller)
Bit 0:
Module has inputs
Bit 1:
Module has outputs
Bit 8-14: Data width internally in
bit 15: 0/1 Analog/digital
module
For analog modules, bits 0-14
identify the module type, e.g., 401
for module 750-401
-