24 System Description
WAGO-I/O-SYSTEM 750 XTR
750-352/040-000 FC ETHERNET G3 XTR
Manual
Version 1.3.0
Pos: 19.16.1 /Serie 750 ( WAGO-I/O- SYST EM)/Systembeschrei bung/Versorgung/Spannungsversorgung - Ü berschrift 2 @ 3\mod_1232950078953_21.docx @ 26680 @ 2 @ 1
3.6
Power Supply
Pos: 19.16.2 /Serie 750 ( WAGO-I/O- SYST EM)/Anschließ en/Ei nspeisekonzepte/XTR-Koppler-/C ontroll er und 750-613/040-000: Einspeisung aus SELV-/PELV-N etzger äten vorgeschrieben @ 29\mod_1495116623787_21.docx @ 422203 @ @ 1
The system power supply and field power supply must be powered via
SELV/PELV power supply units.
Pos: null /Alle Serien ( Allgemei ne Modul e)/Ü berschriften/Ebene 3/Ü berstromschutz - Überschrift 3 @ 31\mod_1523371183064_21.docx @ 481017 @ 3 @ 1
3.6.1
Overcurrent Protection
Pos: null /Serie 750 (WAGO-I/O-SYST EM)/Anschließ en/Einspeisekonzepte/Warnung: Mögliche Brandgefahr durch unzureichenden Ü berstromschutz! (bei Klei nspannung) @ 31\mod_1524745034627_21.docx @ 483789 @ @ 1
Possible fire hazard due to insufficient overcurrent protection!
In the event of a fault, insufficient overcurrent protection can present a possible
fire hazard. In the event of a fault, excessive current flow in the components can
cause significant overheating. Therefore, you should always dimension the
overcurrent protection according to the anticipated power usage.
Pos: null /Serie 750 (WAGO-I/O-SYST EM)/Anschließ en/Einspeisekonzepte/Ü berstromschutz bei Kleinspannung ( XTR) @ 31\mod_1524130657135_21.docx @ 482309 @ @ 1
The system and field voltage of the WAGO I/O SYSTEMs 750 XTR is supplied on
the head stations and bus supply modules.
For components that work with extra low voltage, only SELV/PELV voltage
sources should be used.
A single voltage source supplying multiple components must be designed
according to the component with the strictest electrical safety requirements.
For components which are only allowed to be supplied by SELV voltage sources,
these requirements are listed in the technical data.
Most components in the WAGO-I/O-SYSTEM 750 XTR have no internal
overcurrent protection. Therefore, appropriate overcurrent production must
always be implemented externally for the power supply to these components,
e.g. via fuses.
The maximum permissible current is listed in the technical data of the
components used.
Pos: null /Serie 750 (WAGO-I/O-SYST EM)/Anschließ en/Einspeisekonzepte/Achtung: Systemversorgung nur mit geeigneter Absicher ung! @ 31\mod_1523371427560_21.docx @ 481022 @ @ 1
System supply only with appropriate fuse protection!
Without overcurrent protection, the electronics can be damaged.
If you implement the overcurrent protection for the system supply with a fuse, a
fuse, max. 2 A, slow-acting, should be used.
Pos: null /Serie 750 (WAGO-I/O-SYST EM)/Anschließ en/Einspeisekonzepte/Achtung: Fel dversorgung nur mit g eeigneter Absicherung! @ 31\mod_1523372916706_21.docx @ 481026 @ @ 1
Field supply only with appropriate fuse protection!
Without overcurrent protection, the electronics can be damaged.
If you alternatively implement the overcurrent protection for the field supply with
an external fuse, a 10 A fuse should be used.
Pos: 19.16.8 /Serie 750 ( WAGO-I/O- SYST EM)/Systembeschrei bung/Versorgung/Potenti altrennung @ 3\mod_1232950094125_21.docx @ 26732 @ 3 @ 1