120 Configuring via the Web-Based Management System (WBM)WAGO-I/O-SYSTEM 750 XTR
750-352/040-000 FC ETHERNET G3 XTR
Manual
Version 1.3.0
Table 39: WBM Page “Watchdog”
Connection watchdog
Entry
Default
Description
Connection Timeout Value
(100 ms)
600
Monitoring period for TCP links.
After the completion of this period without any
subsequent data traffic, the TCP connection is
closed.
Modbus Watchdog
Entry
Default
Description
State Modbus Watchdog
Disabled
Enabled – Watchdog is activated
Disabled – Watchdog is disabled
Watchdog Type
Standard
The set coding mask (watchdog trigger mask) is
evaluated to determine whether the watchdog time is
reset.
Alternative
The watchdog time is reset by any Modbus/TCP
telegram.
Watchdog Timeout Value
(100 ms)
100
Monitoring period for Modbus links. After the
completion of this period without receiving a Modbus
telegram, the physical outputs are set to "0".
Watchdog Trigger Mask
(F 1 to F16)
0xFFFF
Coding mask for certain Modbus telegrams (Function
Code FC1 ... FC16)
Watchdog Trigger Mask
(F17 to F32)
0xFFFF
Coding mask for certain Modbus telegrams (Function
Code FC17 ... FC32)