3.6.3
System Supply
Pos: 19.16.12 /Seri e 750 ( WAGO-I/O-SYSTEM)/Systembeschr eibung/Versorgung/Systemversorgung - Anschluss XTR @ 29\mod_1495196287002_21.docx @ 422258 @ 4 @ 1
3.6.3.1 Connection
The WAGO-I/O-SYSTEM 750 requires a 24 V direct current system supply.
The power supply is provided via the fieldbus coupler/controller and, if necessary,
in addition via internal system supply modules “System Power Supply 24 VDC
XTR (750-613/040-000)”. The power supply is reverse voltage protected.
Do not use an incorrect voltage/frequency!
The use of an incorrect supply voltage or frequency can cause severe damage to
the components.
Pos: 19.16.13 /Seri e 750 ( WAGO-I/O-SYSTEM)/Systembeschr eibung/Versorgung/Systemversorgung - Anschluss - Systemversorgung Bil d (neues Gehäuse) XTR @ 18\mod_1392385885615_21.docx @ 145558 @ @ 1
Figure 6: System supply (example)
Table 4: Legend for the “System supply” figure
Pos
.
Description
1
System supply 24 VDC
2
System supply 0 V
Pos: 19.16.14 /Seri e 750 ( WAGO-I/O-SYSTEM)/Systembeschr eibung/Versorgung/Systemversorgung - Anschluss - Di e eingespeiste 24 V-Gl eichspannung versorgt... @ 3\mod_1232950097328_21.docx @ 26756 @ @ 1
The fed-in 24 VDC supplies all internal system components, e.g. fieldbus
coupler/controller electronics, fieldbus interface and I/O modules via the local bus
(5 VDC system voltage). The 5 VDC system voltage is galvanically connected to
the 24 VDC supply voltage.
Pos: 19.16.15 /Seri e 750 ( WAGO-I/O-SYSTEM)/Systembeschr eibung/Versorgung/Systemversorgung - Anschluss - Systemspannung Bil d (EC O - neues Gehäuse) @ 8\mod_1279034845493_21.docx @ 59857 @ @ 1