WAGO-I/O-SYSTEM 750 XTR
Commissioning 85
750-352/040-000 FC ETHERNET G3 XTR
Manual
Version 1.3.0
Pos: 66 /All e Seri en (Allgemei ne Module)/Ü berschriften/Ebene 1/In Betri eb nehmen - Ü berschrift 1 @ 4\mod_1240901452750_21.docx @ 31570 @ 1 @ 1
8
Commissioning
Pos: 67.1 /Serie 750 (WAGO-I/O-SYST EM)/In Betrieb nehmen/Fel dbusknoten i n Betrieb nehmen/In Betrieb nehmen Ei nlei tung - Anfang (Koppler/C ontroll er) @ 4\mod_1238483034921_21.docx @ 29371 @ @ 1
This section shows a step-by-step procedure for starting up exemplarily a WAGO
fieldbus node.
Pos: 67.2 /Serie 750 (WAGO-I/O-SYST EM)/In Betrieb nehmen/Fel dbusknoten i n Betrieb nehmen/Einl eitung - Hi nweis: Exempl arisches Beispi el, 2 erfor derliche Ar bei tsschritte (Koppl er/Contr oller) @ 7\mod_1275300634223_21.docx @ 57223 @ @ 1
Good example!
This description is just an example and only serves to describe the procedure for
a local start-up of a single fieldbus node with a non-networked computer under
Windows.
Two work steps are required for start-up. The description of these work steps can
be found in the corresponding following sections.
•
Connecting PC and fieldbus node
•
Assigning the IP address to the fieldbus node
Pos: 67.3 /Serie 750 (WAGO-I/O-SYST EM)/In Betrieb nehmen/Fel dbusknoten i n Betrieb nehmen/Hi nweis: IP-Adresse muss eindeutig sein! @ 4\mod_1243596850245_21.docx @ 34594 @ @ 1
The IP address must occur in the network only once!
For error-free network communication, note that the assigned IP address must
occur only once in the network!
In the event of an error, the error message “IP address configuration error” (error
code 6 – error argument 7) is indicated by 'I/O' LED at the next power-on.
Pos: 67.4 /Serie 750 (WAGO-I/O-SYST EM)/In Betrieb nehmen/Fel dbusknoten i n Betrieb nehmen/Es gi bt verschiedene M öglichkeiten, di e IP-Adresse zu vergeben. Di ese wer den i n den nachfolg enden K. @ 9\mod_1281682989099_21.docx @ 63563 @ @ 1
There are various ways to assign the IP address.
The various options are described in the following sections individually.
Pos: null /Serie 750 (WAGO-I/O-SYST EM)/In Betrieb nehmen/F eldbusknoten i n Betri eb nehmen/Einl eitung - Anfang - i m Anschl uss sind zusätzliche Themen beschrieben: Flash, U hr, Defaul @ 4\mod_1243521630641_21.docx @ 34197 @ @ 1
Following the commissioning descriptions after which the fieldbus node is ready
for communication, the following topics are described:
•
Preparing the Flash File System
•
Synchronizing the real-time clock
•
Restoring factory settings
Pos: 67.6 /Dokumentation allgemei n/Glieder ungselemente/---Seitenwechsel--- @ 3\mod_1221108045078_0.docx @ 21810 @ @ 1