WAGO-I/O-SYSTEM 750 XTRConfiguring via the Web-Based Management System (WBM)107
750-352/040-000 FC ETHERNET G3 XTR
Manual
Version 1.3.0
Pos: 69.7 /Serie 750 (WAGO-I/O-SYST EM)/Web-Based-Management-System WBM/Seite Infor mation/Infor mation - T abell e (750-330, -352, - 829, -831,-849, -880, - 881) T eil 1 @ 6\mod_1265120976715_21.docx @ 49190 @ @ 1
Table 33: WBM Page “Information”
Coupler details
Entry
Default
Value (example)
Description
Order number
750-352/040-000
750-352/040-000
Order number
Mac address
0030DEXXXXXX
0030DE000006
Hardware MAC address
Firmware
revision
kk.ff.bb (rr)
01.01.09 (00)
Firmware revision number
(kk = compatibility, ff = functionality,
bb = bugfix, rr = revision)
Actual network settings
Entry
Default
Value (example)
Description
IP address
0.0.0.0
192.168.1.80
IP address,
Type of IP address assignment
Subnet mask
255.255.255.0
255.255.255.240
Subnet mask
Gateway
0.0.0.0
192.168.1.251
Gateway
Host name
___
___
Host name (not assigned here)
Domain name
___
___
Domain name (not assigned here)
Pos: 69.8 /Serie 750 (WAGO-I/O-SYST EM)/Web-Based-Management-System WBM/Seite Infor mation/Infor mation - T abell e (750-352, -829, - 831, -849, - 852, - 871,- 880 ,- 884, 889) T eil 2 @ 8\mod_1279001989967_21.docx @ 59694 @ @ 1
DNS server 1
0.0.0.0
0.0.0.0
Address of first DNS server
DNS server 2
0.0.0.0
0.0.0.0
Address of second DNS server
Module status
Entry
Default
Value (example)
Description
State Modbus
Watchdog
Disabled
Disabled
Status of Modbus Watchdog
Error code
0
10
Error code
Error argument 0
5
Error argument
Error description Coupler running, OK KBUS diag error
(Error code 4 / Error
argument 2)
Error description
Pos: 69.9 /Dokumentation allgemei n/Glieder ungselemente/---Seitenwechsel--- @ 3\mod_1221108045078_0.docx @ 21810 @ @ 1