10.1.1 Evaluating Fieldbus Status
The health of the ETHERNET Fieldbus is signaled through the top LED group
('LINK ACT 1, 2', 'MS', und 'NS').
Pos: 73.7.2 /Serie 750 (WAGO-I/O-SYST EM)/Diag nose/Fel dbuskoppl er/-contr oller/F eldbusstatus auswer ten ('LIN K ACT 1, 2', 'M S', 'NS') mit EtherN et/IP - MS und NS für EtherNet/IP @ 9\mod_1282558697263_21.docx @ 64156 @ @ 1
The two-colored LEDs ‘MS’ (module status) and ‘NS’ (network status) are solely
used by the EtherNet/IP protocol. These two LEDs conform to the EtherNet/IP
specifications.
Pos: 73.7.3 /Serie 750 (WAGO-I/O-SYST EM)/Diag nose/Fel dbuskoppl er/-contr oller/F eldbusstatus auswer ten ('LIN K ACT 1, 2', 'M S, 'NS') - T abelle 'LIN K ACT 1, 2', 'MS' @ 9\mod_1282558855632_21.docx @ 64159 @ @ 1
Table 45: Fieldbus Diagnostics – Solution in Event of Error
LED
Status
Meaning
Solution
LINK ACT 1, 2
green
The fieldbus node is connected to the
physical network.
-
green
flashing
The fieldbus node sends and receives
ETHERNET telegrams
-
off
The fieldbus node is not connected to
the physical network.
1. Check the fieldbus cable.
MS
green
Normal operation
-
green
flashing
The system is not yet configures
-
red
The system indicates a not
remediable error
1. Restart the device by turning the power
supply off and on again.
2. If the error still exists, please contact
the I/O support.
red/green
flashing
Self test
-
off
No system supply voltage
1. Check the supply voltage.
NS
green
At least one connection (Modbus
TCP
or EtherNet/IP) is developed (also
connection to the Message rout
applies)
-
green
flashing
No connection (Modbus
TCP or
EtherNet/IP).
-
red
The system indicates a double IP-
address in the network
1. Use an IP address that is not used yet.
red
flashing
At least one connection (Modbus
TCP
or EtherNet/IP) announced a Timeout,
where the controller functions as
target.
1. Restart the device by turning the power
supply off and on again.
2. Develop a new connection.
red/green
flashing
Self test
-
off
No IP address is assigned to the
system.
1. Assign to the system an IP address for
example by BootP or DHCP.