WAGO-I/O-SYSTEM 750
Process Image
51
750-494 3-Phase Power Measurement Module
Manual
Version 1.2.0
Example 2:
Byte Output data
Input data
0 0x00
0x44
1 0x02 (Status query)
0x02
2 0x00
0x40
3 0x09 (COL_ID)
0x09 (COL_ID_SEL)
4 0x06 (MET_ID_1)
0x06 (MET_ID_1_SEL)
5 0x03 (MET_ID_2)
0x03 (MET_ID_2_SEL)
6 0x4E (MET_ID_3)
0x4E (MET_ID_3_SEL)
7 0x17 (MET_ID_4)
0x17 (MET_ID_4_SEL)
8 ---
Voltage, RMS L3-N [7:0]
9
---
Voltage, RMS L3-N [15:8]
10
---
Voltage, RMS L3-N [23:16]
11
---
Voltage, RMS L3-N [31:24]
12
---
Current, RMS L3 [7:0]
13
---
Current, RMS L3 [15:8]
14
---
Current, RMS L3 [23:16]
15
---
Current, RMS L3 [31:24]
16
---
Reactive energy L3 [7:0]
17
---
Reactive energy L3 [15:8]
18
---
Reactive energy L3 [23:16]
19
---
Reactive energy L3 [31:24]
20
---
cos phi L2 [7:0]
21
---
cos phi L2 [15:8]
22
---
cos phi L2 [23:16]
23
---
cos phi L2 [31:24]
The status query was also set in the examples given here. In example 1, the status
query is made for phase L1. No bit is set in the status word (Byte 0) and no error
message is present.
In example 2, the status query is made for phase L3. The status word (Byte 0) is at
0x44, an error has occurred at phase L3 (ERROR, ERR_L3). Byte 2 is at 0x40,
i.e., overvoltage at Phase L3, the set threshold has been exceeded.