118 Appendix
WAGO-I/O-SYSTEM 750
750-494 3-Phase Power Measurement Module
Manual
Version 1.2.0
Table 71: Parameter 40
Parameter 40 – Factor NOLOAD-threshold active energy
Function
Data type
Access
Factory setting
Factor NOLOAD-threshold active energy
UINT
R/W
0x0000 (disabled)
0:
The NOLOAD-threshold is disabled.
1 … 19:
-reserved-
20 … 24000: Factor of the NOLOAD-threshold for calculating
P
THRESHOLD
= (1 / factor) x P
NOMINAL
P
NOMINAL
= 277V x 1A = 277W for the 1A-variants resp.
277V x 5A = 1385W for the 5A-variants
≥24001:
-reserved-
Table 72: Parameter 41
Parameter 41 – Factor NOLOAD-threshold reactive energy
Function
Data type
Access
Factory setting
Factor NOLOAD-threshold reactive energy
UINT
R/W
0x0000 (disabled)
0:
The NOLOAD-threshold is disabled.
1 … 19:
-reserved-
20 … 24000: Factor of the NOLOAD-threshold for calculating
Q
THRESHOLD
= (1 / factor) x Q
NOMINAL
Q
NOMINAL
= 277V x 1A = 277VAR for the 1A-variants resp.
277V x 5A = 1385VAR for the 5A-variants
≥24001:
-reserved-
Table 73: Parameter 42
Parameter 42 – Factor NOLOAD-threshold apparent energy
Function
Data type
Access
Factory setting
Factor NOLOAD-threshold apparent energy
UINT
R/W
0x0000 (disabled)
0:
The NOLOAD-threshold is disabled.
1 … 19:
-reserved-
20 … 24000: Factor of the NOLOAD-threshold for calculating
S
THRESHOLD
= (1 / factor) x S
NOMINAL
S
NOMINAL
= 277V x 1A = 277VA for the 1A-variants resp.
277V x 5A = 1385VA for the 5A-variants
≥24001:
-reserved-