750-494 3-Phase Power Measurement Module
Manual
Version 1.2.0
Pos: 38 /All e Seri en (Allgemei ne Module)/Ü berschriften/Ebene 2/Anzeig eel emente - Ü berschrift 2 @ 4\mod_1240984390875_21.docx @ 31964 @ 2 @ 1
3.3
Display Elements
Pos: 39 /Serie 750 ( WAGO-I/O-SYST EM)/Ger ätebeschrei bung/Anzeigeelemente/Anal ogei ngangsklemmen/Anzeigeel emente 750- 0494, - 0495 @ 16\mod_1371738731125_21.docx @ 123880 @ @ 1
LED A indicates the operating status, LEDs B … H indicate possible errors.
Figure 4: Display Elements
The meaning of these indications is as follows:
Table 7: Legend for Figure “Display Elements”
LED
State
Message
A
Off
No operational readiness or
the internal data bus communication is interrupted.
Note: If the watchdog was disabled, the LED is always
green. See section “Commissioning” > “Configuration
with WAGO-I/O-
CHECK
“.
Green Operational readiness and correct internal data bus
communication
B
Off No error
Red General error message for L1:
Under-/overvoltage or overcurrent
C
Off No error
Red General error message: Clipping of a current measuring
path IL1, IL2 or IL3
D
Off No error
Red High measuring error, caused by undershooting the min.
voltage at L1, L2 or L3
E
Off No error
Red General error message for L2:
Under-/overvoltage or overcurrent
F
Off No error
Red General error message for L3:
Under-/overvoltage or overcurrent
G
Off No error
Red General error message: Clipping of a voltage measuring
path L1, L2 or L3
H
Off No error
Yellow Error of the phase sequence L1-L2-L3