WAGO-I/O-SYSTEM 750
Commissioning
87
750-494 3-Phase Power Measurement Module
Manual
Version 1.2.0
8.1.4
“Energy“ Tab
After entering a password, you can set or reset the energy values per phase on the
"Energy" tab. The initial password is: wago. Please change this password on first
use by clicking
[Change password]
. Should you have forgotten the password
deinstall and install again the application “3-Pase Power Measurement”. This way
the initial password is valid again.
The I/O module registers the energy consumption and saves the values cyclically.
With [
Save
] and [
Delete
] you can save the values at any time regardless the cycle
or reset them to 0.
You can further set a specific value by choosing the energy from the list, entering
a value in milliwatt hours and [
Save
] it. The energy measurement starts at this set
value.
These actions are carried out immediately and cannot be undone. Therefore, the
[Save]
button is disabled at the bottom of the window.
Figure 25: “Energy” Tab