HI 110 / 200 / 300
Operation
ghi_tx001447gb.fm
27
4.7
Positioning the Machine
NOTICE:
Restricting the air flow through the machine during operation can cause
the machine and its components to overheat. To avoid damage, provide adequate
air flow through the machine while it is operating.
Guidelines
Observe the following guidelines when positioning the machine for operation.
Installer must be familiar with all applicable laws, codes, regulations, or other
restrictions regarding installation of Indirect-fired (IDF) heaters.
Machine must be on flat, firm surface.
Installation must adhere to proximity restrictions.
Install wedge blocks under the wheels to prevent movement.
Proximity
restrictions
The machine must be located a safe distance from any other structures, vehicles,
materials or other combustible surfaces. The following proximity restrictions apply
for all machine installations.
20 ft. (6 m) to air outlet
3 ft. (1 m) to air inlet and sides
5 ft. (1.5 m) to top
20 ft (6 m) from outlet to external fuel container
Note:
Graphic is representative only. Your machine may vary.
DANGER
Exhaust gas from the burner contains carbon monoxide, a deadly poison. Exposure
to carbon monoxide can kill you in minutes.
f
Never run the machine indoors or in an enclosed area unless the machine is
vented properly according to local and national codes.
WARNING
Fire hazard. Restricting air flow through the machine during operation can cause a
fire due to overheating components.
f
Do not block the air inlet or outlet during machine operation.