D6032 

- SIL 3 Switch/Proximity Detector Repeater Relay Output         

                                               

G.M. International ISM0405-0 

SIL 3 Switch/Proximity Detector Repeater 

Relay Output, Termination Board 

Models D6032S, D6032D 

 

 D6032S - D6032D 

INSTRUCTION MANUAL 

Summary of Contents for D6032D

Page 1: ...SIL 3 Switch Proximity Detector Repeater Relay Output G M International ISM0405 0 SIL 3 Switch Proximity Detector Repeater Relay Output Termination Board Models D6032S D6032D D6032S D6032D INSTRUCTION MANUAL ...

Page 2: ...mA for 1 channel D6032S with short circuit input and relay energized typical Power dissipation 0 85 W for 2 channels D6032D 0 45 W for 1 channel D6032S with 24 V supply voltage short circuit input and relay energized typical Isolation Test Voltage In Out 2 5 KV In Supply 2 5 KV In In 500 V Out Supply 500 V Out Out 500 V Input switching current levels ON 2 1 mA 1 9 to 6 2 mA range OFF 1 2 mA 0 4 to...

Page 3: ...D6032D used as fault indicator only 2nd ch Systematic capability SIL 3 2 fully independent channels NO NC switch proximity Detector Input NE ND relay actuation mode Field open and short circuit detection Three port isolation Input Output Supply EMC Compatibility to EN61000 6 2 EN61000 6 4 EN61326 1 EN61326 3 1 for safety system In field programmability by DIP Switch TÜV Certification TÜV Functiona...

Page 4: ... R1 R2 used with voltage free contact required for line fault detection MODEL D5032D Duplicator or Fault Out 7 8 Termination board connector Supply 24 Vdc Out 1 SIL3 Out 2 Duplicator or Fault F 9 10 In Proximity voltage free Contact voltage free Contact R1 R2 Resistors R1 R2 used with voltage free contact required for line fault detection Terminals 9 10 must be shorted to set module as Duplicator ...

Page 5: ...lose open and a line open short circuit fault Installation D6032 series are Switch Proximity Detector Interface housed in a plastic enclosure suitable for installation on customized Termination Board D6032 unit can be mounted with any orientation over the entire ambient temperature range Electrical connection of conductors up to 2 5 mm are accommodated by polarized plug in removable screw terminal...

Page 6: ...isabled switch proximity sensor Enabled proximity sensor or switch with end of line resistors de energizes relay in fault condition 7 NO 8 OR NC 7 8 7 NO 8 OR NC 7 8 1 OFF 5 OFF 1 ON 5 ON NE ND Output ND Output NE Position in fault condition 2 ON 2 OFF Input Input Output Input Output Input CH2 Setting Line fault detection IN OUT Operation NO NE or NC ND NO ND or NC NE Disabled switch proximity sen...

Page 7: ...F ON OFF ND Mode NE Mode ON OFF OFF ON Disabled switch proximity sensor Enabled proximity sensor or switch with end of line resistors de energizes relay in fault condition No Fault No Fault 1 OFF 5 OFF 5 ON Output 2 Operation Input Input Output 1 Input Output 1 Input 7 NO 8 OR NC 7 8 7 NO 8 OR NC 7 8 NE ND Output 1 ND Output 1 NE NE ND Set SW4 equal to SW2 Set SW4 opposite to SW2 6 6 ON De energiz...

Page 8: ...figuration 1 2 3 4 7 8 must be set to OFF position 3 4 6 Not used 5 6 7 8 ON CH Setting Line fault detection IN OUT Operation NO NE or NC ND NO ND or NC NE Disabled switch proximity sensor Enabled proximity sensor or switch with end of line resistors de energizes relay in fault condition 1 OFF 5 OFF 1 ON 5 ON Input Input Input Input 7 NO 8 OR NC 7 8 7 NO 8 OR NC 7 8 Output NE Output NE Output ND O...

Page 9: ...dition ON ON ON 1 IN OUT Operation SW2 NO NE or NC ND ON NO ND or NC NE for SIL application OFF Channel 1 2 SW4 ON OFF D6032D used as double channel Configuration Summary Table WARNING dip switch 6 7 8 must be set to OFF position Output 2 Operation SW6 SW7 SW8 Mode SW4 Duplicator De energized in fault condition for SIL application if line fault detection enabled SW1 ON ON OFF ON Parallel for SIL a...