5.7.3 The most important basic rules to guarantee EMC
In order to guarantee EMC, it often suffices when one keeps to a few elementary rules. Therefore
observe the following guidelines when constructing the controls:
•
=
Ensure that you use a good configured two-dimensional earth of inactive metal parts when
setting up an automation piece of equipment.
-
Establish a central connection between the ground and the earth electrode/protective
earth conductor system.
-
Connect all inactive metal parts on a large area and with little impedance.
-
Use no aluminium parts if possible. Aluminium oxidises easily and is therefore less
suitable for the earth.
•
=
Ensure to have a proper cable tracing when wiring.
-
Divide the cabling into cable groups.
(Heavy current, current supply cables and signal and data cables).
-
Always lay the heavy current cables and the signal and data cables in separate
channels or bundles.
-
Lead the signal and data cables as tight as possible on the ground area
(e.g. supporting bars, metal rails, thin metal barriers).
•
=
Ensure to fasten the cable screens perfectly.
-
Data cables are to be laid shielded. The screen is to be applied on both sides.
-
Analogue cables are to be laid shielded. The laying of screens on one side can be
advantageous when transmitting signals with small amplitudes.
-
Lay the cable screens largely on a screen/protective earth conductor rail after the
barrier entry and secure the screens with cable clamps.
-
Ensure that the screen/protective earth conductor rail is connected with little
impedance to the barrier.
-
Use metallic or metallized connector housing for screened data cables.
•
=
Use special EMC measures in particular application cases.
-
Wire all inductances with capacities, which are not controlled by VIPA
building
blocks.
-
Use incandescent lamps to illuminate the barriers and avoid fluorescent
lamps.
•
=
Create a uniform reference potential and earth all resources where possible.
-
Be aware of the intended input of earthing measures. The earthing of the control
serves as a protection and functional measure.
-
Connect the plant parts and barriers with the central and expanded equipment in
stelliform with the earth/protection earth conductor system. The formation of earth
loops is therefore prevented.
-
Lay in potential differences enough dimensioned potential equalization cables
between plant parts and barriers.
Summary of Contents for SSM-BG41
Page 2: ...Lerrzeichen...
Page 8: ...Contents Manual BG41 BG42 BG43 iv Rev 99 49...
Page 10: ......
Page 16: ......
Page 26: ...Firmware s memory distribution Manual BG41 BG42 BG43 2 10 Rev 99 49...
Page 28: ......
Page 53: ...Manual BG41 BG42 BG43 Interface modules Rev 99 49 3 25 3 2 7 2 Data flow Fig 3 26 Data flow...
Page 114: ...Functional description and allocation of terminal pins Manual BG41 BG42 BG43 3 86 Rev 99 49...
Page 116: ......
Page 215: ...Manual BG41 BG42 BG43 Software Rev 99 49 4 99 Month 06h Year 95h Weekday Tuesday 02h...
Page 222: ...Application of interfaces without data handling blocks Manual BG41 BG42 BG43 4 106 Rev 99 49...
Page 224: ......
Page 258: ...Structure guidelines Manual BG41 BG42 BG43 5 34 Rev 99 49...
Page 260: ......
Page 274: ...Overview cycle load Manual BG41 BG42 BG43 6 14 Rev 99 49...
Page 275: ...Appendix A List of figures A 1 B Index of tables B 1 C Index C 1...
Page 276: ......
Page 280: ...List of figures Manual BG41 BG42 BG43 A 4 Rev 99 49...