![VIPA SSM-BG41 Manual Download Page 171](http://html1.mh-extra.com/html/vipa/ssm-bg41/ssm-bg41_manual_1029239171.webp)
Manual BG41/BG42/BG43
Software
Rev. 99/49
4-55
4.1.8.6 FB20 (SYNCHRON) up to firmware 4.1 for 3964(R) with RK512
This data handling block prepares the interface building block for the operation of the procedure
3964(R).
The block supports the procedure 3964(R) with the RK512 protocol. The data handling block must
be loaded in all start branches (OB20,21,22) for each interface to be used. If two channels are used
with the procedure 3964(R), this data handling block must be loaded twice.
The data handling block possesses formal operands.
Several working parameters are to be set through these formal operands. They can only be directly
addressed.
The following parameters are to be transmitted when loading FB20:
Bez.
Format
Erklärung
ADRE
KH
The address set with DIL switches
SSNR
KF
Interface number 1,2 (3)
BAUD
KF
Baud rate code 1...11 (10 = 9600baud)
FORM
KM
Transmission format:8bit,even parity,2 stop
PRIO
KF
0=low, 1=high priority
BLOC
KF
Block size in bytes (always even-numbered!)
PAFE
MB
Byte for the output of an error number
Tab. 4-16:List of parameters for the loading of FB20
The following details are necessary for the abovementioned parameters:
ADRE
Input of the physical start address, under which the building block can be
accessed by the PLC. This start address can be set with the DIL switches S1 and
S2 (see chapter 5).
SSNR
The interface number 1 or 2 are to be given. By the firmware 4017, number 3 can
also be given.
BAUD
Different baud rates can be set by inputting the respective codes. With the plug
connector J11 on the building block, optional baud rates from 150 to 38400 baud
can be set. In order to achieve this, J11 which has a baud rate of 75 to 19200 baud
in its delivery state, must be replugged.
Summary of Contents for SSM-BG41
Page 2: ...Lerrzeichen...
Page 8: ...Contents Manual BG41 BG42 BG43 iv Rev 99 49...
Page 10: ......
Page 16: ......
Page 26: ...Firmware s memory distribution Manual BG41 BG42 BG43 2 10 Rev 99 49...
Page 28: ......
Page 53: ...Manual BG41 BG42 BG43 Interface modules Rev 99 49 3 25 3 2 7 2 Data flow Fig 3 26 Data flow...
Page 114: ...Functional description and allocation of terminal pins Manual BG41 BG42 BG43 3 86 Rev 99 49...
Page 116: ......
Page 215: ...Manual BG41 BG42 BG43 Software Rev 99 49 4 99 Month 06h Year 95h Weekday Tuesday 02h...
Page 222: ...Application of interfaces without data handling blocks Manual BG41 BG42 BG43 4 106 Rev 99 49...
Page 224: ......
Page 258: ...Structure guidelines Manual BG41 BG42 BG43 5 34 Rev 99 49...
Page 260: ......
Page 274: ...Overview cycle load Manual BG41 BG42 BG43 6 14 Rev 99 49...
Page 275: ...Appendix A List of figures A 1 B Index of tables B 1 C Index C 1...
Page 276: ......
Page 280: ...List of figures Manual BG41 BG42 BG43 A 4 Rev 99 49...