Handling with VIPA data handling blocks
Manual BG41/BG42/BG43
4-64
Rev. 99/49
4.1.8.8 FB23 (SEND), data output for 3964(R) with RK512
This data handling block is used to actively transmit a telegram to the interface building blocks
BG41, BG42 und BG43 when using the procedure 3964(R) with the RK512 protocol.
Lubricating flags are used in FB23. These must be saved before loading the
FB23 from a time or alarm protected OB.
The data handling block posseses formal operands.
Several working parameters are to be set through these formal operands. They can be directly as
well as indirectly parametrized.
The following parameters are to be transmitted when loading FB23:
Des.
Format
Explanation
ADRE
KH
The address set with the DIL switches
SSNR
KF
Interface number 1,2 (3)
A-NR
KF
Order number (1...255)
QTYP
KC
Source type
QDBN
KY
DB no. by source type DB or DX
QBWN
KY
Byte/word number from which data is to be sent.
BWAN
KF
Amount of data to be sent
ZTYP
KC
Target type for the telegram in the PLC
ZDBN
KY
DB no. by target type DB
ZBWN
KY
Byte/word from where data is to be written
KOOR
KY
Coordination flags
ANZW
MW
The display word is filed in this word.
PAFE
MB
Error messages in relation to parametrizing are filed in this
byte.
NEUS
M
New start bit
Tab. 4-18:List of parameters for the loading of FB23
The following details are necessary for the abovementioned parameters:
ADRE
Input of the physical start address, under which the building block can be
accessed by the PLC. This start address can be set with the DIL switches S1 and
S2 (see chapter 5).
SSNR
The interface number 1 or 2 is to be given. By the firmware 4017, the number 3
may also be given.
A-NR
Order Number, a number in the area of 1...255. This number may not be given to
any other data handling block.
Summary of Contents for SSM-BG41
Page 2: ...Lerrzeichen...
Page 8: ...Contents Manual BG41 BG42 BG43 iv Rev 99 49...
Page 10: ......
Page 16: ......
Page 26: ...Firmware s memory distribution Manual BG41 BG42 BG43 2 10 Rev 99 49...
Page 28: ......
Page 53: ...Manual BG41 BG42 BG43 Interface modules Rev 99 49 3 25 3 2 7 2 Data flow Fig 3 26 Data flow...
Page 114: ...Functional description and allocation of terminal pins Manual BG41 BG42 BG43 3 86 Rev 99 49...
Page 116: ......
Page 215: ...Manual BG41 BG42 BG43 Software Rev 99 49 4 99 Month 06h Year 95h Weekday Tuesday 02h...
Page 222: ...Application of interfaces without data handling blocks Manual BG41 BG42 BG43 4 106 Rev 99 49...
Page 224: ......
Page 258: ...Structure guidelines Manual BG41 BG42 BG43 5 34 Rev 99 49...
Page 260: ......
Page 274: ...Overview cycle load Manual BG41 BG42 BG43 6 14 Rev 99 49...
Page 275: ...Appendix A List of figures A 1 B Index of tables B 1 C Index C 1...
Page 276: ......
Page 280: ...List of figures Manual BG41 BG42 BG43 A 4 Rev 99 49...