Value x is the loop number (2 onwards).
245.248.0 Common Scan Fail
Indicates unable to communicate with one or more AS 1668 fan
control PCBs that have been configured.
245.248.1 Common CRC Fault Indicates CRC fault reported from one or more AS 1668 fan
control PCBs.
245.248.2 Foreign Control
Indicates unconfigured AS 1668 fan control PCBs detected.
The above points are allocated for AS 1668 fan controls when the
equipment number 248 for fan controls or other DSS functions is
configured.
Point
Point
Description
Description
246.1.0
Scan Fail
This point is placed into fault if the
MX1
does not receive valid
replies from the Remote FBP.
246.1.1
Enable
This point determines if the keypad on the Remote FBP is
enabled. If the operate state is true, the keypad will be enabled
and accept keypresses.
246.1.2
LED Board
This point is placed into fault when the Remote FBP detects an
LED board fault.
246.1.3
Keyboard
This point is placed into fault when the Remote FBP detects a
fault on the keypad.
246.1.4
Ext Fault
This point is placed into fault when the Remote FBP external fault
input has been activated.
246.1.5
Micro Test
This point is placed into fault when the Remote FBP micro test
fails.
246.1.6
CRC Fail
This point is placed into fault when the Remote FBP program
CRC check fails.
246.1.7
RAM Test
This point is placed into fault when the Remote FBP RAM test
fails.
246.1.8
Channel A
This point is placed into fault when communication channel A is
detected to be in fault. Currently not implemented.
246.1.9
Channel B
This point is placed into fault when communication channel B is
detected to be in fault. Currently not implemented.
246.1.10 Access Level 2
This point determines whether the menu for the Remote FBP will
be in Access Level 2. If the operate state is true, menu level 2
access is enabled.
246.1.11 Alarm Buzzer
This point shows the state of the alarm buzzer on the Remote
FBP, which is controlled directly by internal logic. ActInput
indicates that the alarm buzzer is active.
246.1.12 Fault Buzzer
This point shows the state of the fault buzzer on the Remote FBP,
which is controlled directly by internal logic. ActInput indicates
that the fault buzzer is active.
246.1.13 LCD Fault
This point is placed into fault when the Remote FBP LCD fails.
246.1.14 Buzzer Disable
This point indicates as Disabled when the buzzer has been
disabled, and TestOp when the buzzer is muted.
246.2.0
through
to
246.19.0
Switch Input n
This point is placed into ActInput if switch input n on the keypad is
active.
Equipment
245
– Fan Control
Boards
Equipment
246
– Remote
FBP