Vigilant
MX1-Au
Operator Manual
Document: LT0439
Page
23 October 2018
Issue 1.73
4-4
The
<event text>
is one of the following:
Zone Events Text
Event Text
Meaning
Activate
This zone has become Active (distinct from Alarm
state). Output points mapped to the zone become
operated.
Alarm
One or more of the detectors in this zone has gone into
Alarm.
Alarm ACK'D
The alarm on this zone has been acknowledged by a
user.
Alarm clear
The alarm on this zone has cleared.
Alarm Test
Start
A test of the processing of alarm conditions in this zone
has been started.
Auto Reset Test
Auto-Reset mode has been started for this zone.
Auto Reset
Timeout
Auto-Reset mode for this zone has been cancelled due
to a timeout period with no new alarms.
Bad Event
The event code wasn’t recognised by this panel.
Deactivate
This zone has stopped being Active.
De-operate
All output devices in this zone have been switched out
of the operated condition.
Disable/Enable
This zone has been disabled/enabled by an operator
command respectively.
Fault
One or more of the devices in this zone is faulty.
Fault clear
All faults on this zone have cleared.
Fault Test
Start
A test of the processing of fault conditions in this zone
has been started.
Fault Test Stop
A fault test has been terminated by an operator.
First alarm
A detector mapped to this zone has signalled alarm,
but the zone alarm is not signalled yet because the
alarm is being investigated (AAF alarm) or a second
point in alarm is required (the zone is programmed for
dual-hit operation).
Input activated
Input
deactivated
An input point mapped to this zone has become Active
(distinct from Alarm) or has stopped being Active,
respectively.
Normal
This zone has returned to normal.
Operate
One or more non-disabled output devices in this zone
have been switched into the operated condition.
Operate Test
Start
An Operate Test command has been issued for this
zone. This will result in all th
e zone’s output points
being test-operated.
Pre-alarm
One or more of the detectors in this zone is in a pre-
alarm condition.
Pre-Alarm clear
The pre-alarm condition on this zone has cleared.
Reset
This zone has been reset by an operator command.
Test Abort
The current test on this zone has been cancelled.
Test Fail
The current test on this zone has failed.
Test Pass
The current test on this zone has passed.