Document: LT0439 Vigilant
MX1-Au
Operator Manual
Issue 1.73
23 October 2018
Page 12-15
Point Number Point Text Description
241.34.0
NIC Panel
Connection
Provides status of the
MX1
connection to other network interface
devices. Fault indicates that communication is not possible
–
usually because the wrong serial port is used, the connection is
broken, the wrong baud rate is selected, or the network interface,
device is turned off.
Refer to
NETWORK CONNECTION STATUS
below for
descriptions of the text displayed.
NETWORK CONNECTION STATUS
DISPLAYED TEXT
DESCRIPTION
Normal
The connection to the I-HUB, PIB or Other network interface
device is working correctly.
Disabled
The connection to the network interface has been disabled.
Fault Type Mismatch
The network interface detected does not match the interface
configured in the
MX1
panel’s database.
Fault
The connection to the network interface has failed.
Fault Duplicate SID
Another device on the network has the same SID number as
the
MX1
.
The status of these points is generated by specific programming in the
configuration.
The default AS1668 logic creates a pseudo point 242.255.0 (AS1668
Common Fault) which will create a fault condition on the
MX1
when any
AS1668 control indicates a fault condition.
Point
Point
Description
Description
243.1.0
Scan Fail
This point is placed into fault if the
MX1
does not receive valid
replies from the LCD/keyboard.
243.1.1
Enable
This point determines whether the LCD/keyboard will be set up to
ignore or accept keypresses from the keypad. If the operate state
is true, the keypad will be enabled and accept keypresses.
243.1.2
LED Board
This point is placed into fault when the LCD/keyboard detects an
LED board fault.
243.1.3
Keyboard
This point is placed into fault when the LCD/keyboard detects a
fault on the numeric keypad.
243.1.4
Ext Fault
This point is placed into fault when the LCD/keyboard external
fault input has been activated.
243.1.5
Micro Test
This point is placed into fault when the LCD/keyboard micro test
fails.
243.1.6
CRC Fail
This point is placed into fault when the LCD/keyboard program
CRC check fails.
243.1.7
RAM Test
This point is placed into fault when the LCD/keyboard RAM test
fails.
243.1.8
Channel A
This point is placed into fault when communication channel A is
detected to be in fault. Currently not implemented.
243.1.9
Channel B
This point is placed into fault when communication channel B is
detected to be in fault. Currently not implemented.
Equipment 242
– Pseudo
Points
Equipment
243
– LCD/
Keyboard