Document: LT0439 Vigilant
MX1-Au
Operator Manual
Issue 1.73
23 October 2018
Page 12-19
Point
Point
Description
Description
246.20.0
through
to
246.35.0
Open Collector
Output n
This point drives the open collector output n on the Remote FBP.
Its operate state can be driven by the mapped zone's operate
state or by logic.
246.36.0 FRC Monitor
This point is placed into fault when the FRC to the 26 way Switch
Input connector is removed.
246.36.1 Switch Input set 0
Monitor
This point is placed into fault when at the Remote FBP the end-
of-line resistor is missing from switch input set 0, which contains
inputs 16-18.
246.36.2 Switch Input set 1
Monitor
This point is placed into fault when at the Remote FBP the end-
of-line resistor is missing from switch input set 1, which contains
inputs 1-3.
246.36.3 Switch Input set 2
Monitor
This point is placed into fault when at the Remote FBP the end-
of-line resistor is missing from switch input set 2, which contains
inputs 4-6.
246.36.4 Switch Input set 3
Monitor
This point is placed into fault when at the Remote FBP the end-
of-line resistor is missing from switch input set 3, which contains
inputs 7-9.
246.36.5 Switch Input set 4
Monitor
This point is placed into fault when at the Remote FBP the end-
of-line resistor is missing from switch input set 4, which contains
inputs 10-12.
246.36.6 Switch Input set 5
Monitor
This point is placed into fault when at the Remote FBP the end-
of-line resistor is missing from switch input set 5, which contains
inputs 13-15.
246.37.0 Fire Protection
Active
When this point is placed into the Operate state by a logic
equation the corresponding indicator on the Remote FBP turns
ON.
246.37.1 Smoke Control
Active
When this point is placed into the Operate state by a logic
equation the corresponding indicator on the Remote FBP turns
ON.
246.37.2 Spare Indicator
When this point is placed into the Operate state by a logic
equation the corresponding indicator on the Remote FBP turns
ON.
246.37.3 Spare Indicator A
NOT SUPPORTED
246.37.4 Spare Indicator B
NOT SUPPORTED
Point
Point
Description
Description
247.x.0
SID Comms Status Provides the communication status of the remote SID.
247.x.1
SID MAF Status
Displays the MAF status of the remote SID. Refer to page 9-8
for the MAF Status text displayed.
247.x.2
NIC Fault Status
For SIDs that support this, displays the fault status of the remote
network interface (an I-HUB). Refer to the descriptions for the
points 241.32.1 through 241.32.13 (earlier in this section) for an
explanation of the faults that can appear.
247.x.3
NIC Warning Status For SIDs that support this, displays the warning status of the
remote network interface (an I-HUB). Refer to the descriptions
for the points 241.32.1 through 241.32.13 (earlier in this section)
for an explanation of the warnings that can appear.
Value x is the SID number.
Equipment
247
– SID Points