Vigilant
MX1-Au
Operator Manual
Document: LT0439
Page
23 October 2018
Issue 1.73
12-12
Point Number Point Text Description
241.27.3
FW CRC
Provides the status of the controller firmware. The point state is
Fault if a CRC check of the firmware fails, otherwise the state is
Normal.
241.27.4
RAM Test
Provides the status of the Controller boards RAM. The point
state is Fault if an error is detected with the RAM, otherwise the
state is Normal.
241.27.5
Auto Test
Point is unused but included for future enhancement.
241.27.6
Self Test
Point is unused but included for future enhancement.
241.27.7
Cold Start
Point is unused but included for future enhancement.
241.27.8
Warm Start
Point is unused but included for future enhancement.
241.27.9
Foreign
RZDU
This point indicates that there are one or more foreign RZDUs
detected in the system. The point state is Fault if a reply is
received from an RZDU with an address that corresponds to an
RZDU that is not enabled in the configuration data file. The fault
will automatically clear if replies from the foreign RZDU stop
being received.
241.27.10
Commission
Test
Provides status of the
MX1
Commission Test function, for recall
on the LCD and to light the Tests indicator on the keypad. When
Commission Mode is active, the status of this point will show
ActInput and TestOp. Otherwise it will show Normal.
241.27.11
Startup Flags This point signals Fault for 12 seconds following restart of the
panel. This includes cold starts, user initiated reboots, and
system controlled or uncontrolled watchdog restarts. The Startup
Flags status can be used to ensure that a fault is sent to the
brigade signalling equipment, or not.
241.27.12
Output Logic This point signals fault if the
MX1
has what appears to be an
uncorrupted configuration data file but which contains compiled
Output Logic with fatal problems. If this fault is signalled, the
ability of the
MX1
to act as a fire alarm is severely compromised.
The
MX1
firmware will force the System Fault and Faults
indicators on, and will force the fault relay into its de-energised
state. This fault can only be corrected by restarting the panel
using a configuration data file with output logic compiled without
the problem, which could be either the alternative configuration
data file stored in the
MX1
or a newly downloaded configuration
data file.
241.27.13
Panel
Attended
This point signals when the AIF is in attended mode.
241.27.14
Printer output This point is disabled if the printer output is disabled.
241.28
ISO Sys
Fault
Point is unused but included for future enhancement.
241.29.0
Sil Alms
Not used in Australia.
241.29.1
Trial Evac
Not used in Australia.
241.29.2
Services
Restore
Not used in Australia.
241.29.3
Auto Dis.
Zones Pres
Not used in Australia.
241.30.0
Common
Routing
Provides the common status of the routing outputs. The status
will show Alarm when the Alarm routing output should be
activated, ActInput when the Fault or Disables routing outputs
should be activated. It will become disabled when all of the
Alarm, Fault and Disables routing points are disabled. It cannot
be enabled until at least one of those points becomes enabled.