Document: LT0439 Vigilant
MX1-Au
Operator Manual
Issue 1.73
23 October 2018
Page 11-31
Figure 11-31 shows the mounting of the PIB in the 8U cabinet with a
Moxa switch mounted on the FP1013 mounting bracket.
Figure 11-31
–
8U Cabinet PIB Mounting
Figure 11-32 shows the 3 mounting positions for the PIB on the 15U
gearplate. Position 1 is recommended because it provides the required
earth facilities.
Figure 11-32 – 15U Cabinet PIB Mounting Positions
When mounting the PIB in position 2, earth leads will need to be fitted
between earth tabs J23 and J25 and the gearplate. When mounting the
PIB in position 3 an earth lead will be required to be fitted between earth
tab J25 and the gearplate. No earth lead is required for J23 as there is a
metal standoff on the gearplate.
A Moxa switch and one Ethernet extender (or 2 Ethernet extenders) can
be mounted using one FP1012 mounting bracket. This bracket is
mounted on the left side of the gearplate, as shown in Figure 11-33.
PIB
Moxa
Switch
FP1013
Bracket
PIB Position 1
(recommended)
PIB Position 3
PIB Position 2