12-10
Point Number Point Text Description
241.21
DOOR
Provides the status of the door input which uses a clean contact
switch to monitor the door open/closed status. Normal (closed) is
S/C to 0V, ActiveInput (open) is O/C.
241.22
FW WR EN
Provides the status of the "Firmware Write Enable" jumper.
ActiveInput when jumper is fitted, Normal when not fitted.
241.23
DB WR EN
Provides the status of the "Database Write Enable" jumper.
ActiveInput when jumper is fitted, Normal when not fitted.
241.24.0
Batt Voltage Point is unused but included for future enhancement.
241.24.1
PSU I
Point is unused but included for future enhancement.
241.24.2
PSU V
Point is unused but included for future enhancement.
241.25.0
Mains
Provides the state of the mains power supply to the panel. This
point is placed into Fault when the mains power has failed, and
Normal otherwise.
241.25.1
Batt Low
Indicates battery voltage low level. Point will be in Fault when the
battery voltage drops below the threshold set in the
configuration, and Normal otherwise.
241.25.2
Batt Conn
Indicates battery connectivity. The state is Normal if the battery is
found to be connected or Fault if the battery is disconnected or
very discharged.
241.25.3
Earth
Indicates earth monitoring fault condition. Point will be in Fault
when an earth fault is detected, Normal otherwise.
241.25.4
Battery Test Indicates battery test state. Point will be in ActiveInput when
battery test is active, Normal otherwise.
241.25.5
VBF1 Fuse
Provides the status of the fuse (F3) protecting the ANC1 power
supply (J4-1). Normal indicates the fuse is intact, Fault indicates
that the fuse has blown or is not fitted.
241.25.6
VBF2 Fuse
Provides the status of the fuse (F4) protecting the ANC2 power
supply (J5-1). Normal indicates the fuse is intact, Fault indicates
that the fuse has blown or is not fitted.
241.25.7
VBF3 Fuse
Provides the status of the fuse (F5) protecting the ANC3 power
supply (J6-1). Normal indicates the fuse is intact, Fault indicates
that the fuse has blown or is not fitted.
241.25.8
RZDU Fuse Provides the status of the fuse (F2) protecting the RZDU power
supply (J24-1). Normal indicates the fuse is intact, Fault indicates
that the fuse has blown or is not fitted.
241.25.9
Battery
Capacity
Indicates that the long-term battery test has failed. Point will be in
Fault while test is running and has failed, Normal otherwise.
241.25.10
VNBF Fuse
Provides the status of the fuse (F6) protecting the non-battery
backed power supply (J15-1). Normal indicates the fuse is intact,
Fault indicates that the fuse has blown or is not fitted.
241.25.11
Charger High Provides indication of whether the charger voltage is higher than
it should be. The threshold is determined by the Charger High
voltage setting in the configuration. Normal indicates the charger
voltage is less than the specified voltage, Fault indicates that the
charger voltage is too high.
241.25.12
Charger Low Provides indication of whether the charger voltage is lower than it
should be. The threshold is determined by the Charger Low
voltage setting in the configuration. Normal indicates the charger
voltage is higher than the specified voltage, Fault indicates that
the charger voltage is too low.