53
Coding in the delivered condition
Possible change
Pump control in "Standby mode"
F7:25
In the "Standby" operat-
ing mode, the circulation
pump in the heating cir-
cuit connection set is per-
manently ON (only for
constant temperature
control units)
F7:0
In the "Standby" operating
mode, the circulation pump
in the heating circuit con-
nection set is permanently
OFF
F7:1
to
F7:24
In the "Standby" operating
mode, the circulation pump
in the heating circuit con-
nection set will be started 1
to 24 times per day for
10 min respectively
Start temperature raising
F8:-5
Temperature limit for ter-
minating the reduced
mode -5 ºC, see example
on page 130.
Observe the setting of
coding address "A3" (only
for weather-compensa-
ted control units)
F8:+10
to
F8:-60
Temperature limit adjusta-
ble from
+10 to -60 °C
F8:-61
Function disabled
End temperature raising
F9:-14
Temperature limit for rais-
ing the reduced set room
temp. -14 ºC, see exam-
ple on page 130 (only for
weather-compensated
control units)
F9:+10
to
F9:-60
Temperature limit for rais-
ing the set room tempera-
ture to the value selected
for standard mode adjusta-
ble from
+10 to -60 °C
Increase set flow temperature
FA:20
Raising the set boiler
water temperature or the
set flow temperature
when changing from
operation with reduced
room temperature to
operation with standard
room temperature, by
20 %. See example on
page 131 (only for
weather-compensated
control units)
FA:0
to
FA:50
Temperature rise adjusta-
ble from 0 to 50 %
Code 1
Heating circuit 1, heating circuit 2, heating…
(cont.)
5692 843 GB